Ultrasonic Level Meter
Operation Manual
Medium speed: the parameters are between those for slow speed and fast
speed;
Fast speed: the response rate is fast and measuring accuracy is low, very easy
to be disturbed. The factory default is medium speed.
3.Safe Level(Safe material level)
: there are four optional items, i.e. remaining,
minimum value, maximum value and setting value.
Remaining: the display value is the final measured value before wave loss, and
the current is the corresponding value;
Minimum: the display value is 4mA after wave loss, and the current 4mA;
Maximum: the display value is 20mA after wave loss, and the current 20mA;
Setting value: the display value is the final measured value after wave loss, and
the current output is the setting value of setting current. The factory default is
the remaining value.
4.
Current Set(Set current):
set the output current after wave loss, which shall
be more than 3.6mA and less than 22mA, and become invalid in case of
remaining/minimum/maximum values on reselection. The factory default is
3.6mA.
◆
"4 Transducer Set(Set probe)" (do not modify this parameter)
Select probe and set relevant parameters.
1 Transducer Type(Probe selection):
1~9 options. Select the probe according
to label on it. Factory default is 5.