Startup Adjustments
70
Ecos
aire
®
July 2007
Data subject to change without notice.
With the compressor running, check that refrigerant sight glass
is full.
Check the suction pressure and the discharge pressure at the
compressor. The suction pressure should be above 50 PSI. If it
is not above 50 PSI, stop and determine the cause.
The discharge pressure should be 250 PSI ± 15 PSI. If it is
not, then check that the coling fluid temperature and flow rate
are within specifications.
Air-Cooled Direct Expansion, Water-Cooled Direct Expansion, Glycol-Cooled
Direct Expansion, Air-Cooled DualCool, Glycol-Cooled DualCool,
& FreeCool Units Only