Press
↓
to access the humidity alarm set point screen. The humidity alarms are
factory set for High=80% and Low=20%. If the room temperature goes over
“High” or under “Low” for a period greater than “Delay”, an alarm will be regis-
tered. Unit operation will not be affected. These settings can be changed as
below.
To select the alarm set point to change, press
↵
repeatedly to move the cursor to
the desired position. The example is for the High humidity alarm set point.
To change the set point, press either the
↑
or the
↓
button.
To store the new value, press
↵
repeatedly to move the cursor back to the top left
corner.
Humidity Alarms
High = 80.0%RH
Low = 20.0%RH
Delay = 015 sec
Humidity Alarms
High = 80.0%RH
Low = 20.0%RH
Delay = 015 sec
Humidity Alarms
High = XX.X%RH
Low = 20.0%RH
Delay = 015 sec
Humidity Alarms
High = XX.X%RH
Low = 20.0%RH
Delay = 015 sec
Startup Pre-Startup Adjustments Humidity Set Points
Press
↓
repeatedly to access Humidity Set Points.
To access the humidity set point
screen, press
↓
three times.
To select the humidity set point press
↵
to move the cursor to the set point.
To change the humidity set point, press either the
↑
or the
↓
button to select the
desired temperature. The longer the button is held, the faster the set point
changes.
To store the new set point, press
↵
. The cursor moves to the top left corner.
Press
Prg
, enter the password, and press
↵
, as discussed in
Startup - Pre-
startup Adjustments - Controller Password
. The screen will appear as
shown.
System ON/OFF
System = OFF
Note: This adjustment requires the user password, see Startup - Pre-startup
Adjustments - Controller Password.
Humidity set pts
Set point xx.x%rh
Humidity set pts
Set point XX.X%rh
Humidity set pts
Set point XX.X%rh
Humidity set pts
Set point XX.X%rh
Prg
Esc
ST