Ecos
aire
®
CM Series Precision Air Conditioner Owners Manual
62
Ecos
aire
®
July 2007
Data subject to change without notice.
The refrigerant expansion valves must be adjusted at startup.
Firmly attach a thermocouple or other temperature sensor to the suction
tube.
Insulate the sensor and all around the suction tube with 1/2” thick
insulation for at least three inches on either side of the temperature sensor.
Tape the insulation to prevent air flow from changing the temperature
reading.
Locate and identify the refrigerant sight glass.
Locate and identify the expansion valve.
Suction Tube
Startup Prepare to Adjust Expansion Valves
Expansion Valve
Attach temperature sensor here. Route the sensor
cable out of the cabinet. Replace the access panel.
Air-Cooled Direct Expansion, Water-Cooled Direct Expansion, Glycol-Cooled
Direct Expansion, Air-Cooled DualCool, Glycol-Cooled DualCool,
& FreeCool Units Only