CM Series Precision Air Conditioner Owners Manual
Product Description Major Cooling Options
10
Ecos
aire
®
July 2007
Data subject to change without notice.
chilled water
or other fluid,
(by others)
Glycol-Cooled DualCool
Normally, heat is transferred to
a flow of chilled water (by others).
DualCool units include a three-
way proportional chilled-water
valve, balanced bypass line, flow
switch and water-temperature
sensor. All are factory mounted
to copper piping for a standard
working-pressure rating of 400
psig (2758kPa), ideal for high-rise
buildings.
The unit is rated for use with
45°F (7.2°C) chilled water. For
flow rates and other details, see
Installation - Piping
.
If the flow rate or temperature of the
chilled water becomes inadequate for
proper operation, the unit will automatical-
ly change to Glycol-Cooled Direct-
Expansion.
Glycol coolers are available for the fol-
lowing ambient conditions:
Design
Temp.
95°F (35°C)
100°F (37.8°C)
105°F (40.6°C)
Ecosaire
CM
Ecosaire
CM
Remote Glycol Cooler
Remote Glycol Cooler
service isolation
valves (by others)
service isolation
valves (by others)
DESCRIPTION
SAMPLE
Number
, location, and
appearnce of component
s
may vary
.