Table 3-4 Run Lamp
3.8.13 All of the hoists have speed/frequency ranges that can be customized to a specific application.
Refer to
Table 3-5
for specific hoist speed/frequency ranges. To set custom speeds for an
application, follow the procedure listed in
Table 3-6
and refer to the speed/frequency
Table 3-7
.
Table 3-5 Hoist Speed and VFD Frequency Ranges
200V = 208 – 230V / 400V = 415 – 460V
Product
Code
Lifting Speed
1
(ft/min)
VFD Frequency
1
(Hz)
Low
High
No Load
High
Speed
2
Low (d1-01)
High (d1-02)
200V 400V 200V 400V
RY030
4.3
26
39
8.5
8.6
57.7
56.5
RY050
4.3
26
39
8.3
8.4
56.5
57.5
1)
The factory standard minimum and maximum speed/frequency range (6:1 ratio).
2)
The “Light-Load High Speed” feature is not an adjustable parameter. It can be
turned on/off using the instructions in
Table 3-8.