KIPI ecoMAX920 P1-CH Operating And Installation Manual Download Page 25

25 

 

 

Example  of  connecting  an  external  alarm  device:  1  - 

regulator,  2  -  external  alarm  device,  3  -  relay  RM  84-
2012-35-1012.

 

5.8

 

Connecting the damper actuator 

The air damper actuators are connected in 
accordance with the electric diagram. The 
regulator cooperates only with single-phase 
air damper actuators of the open / close type 
(ON-OFF). 
 

5.9

 

Connecting the STB temperature 
limiter 

If  the  furnace  temperature  exceeds  95  °  C, 
the  power  supply  to  the  fuel  feeder  and  the 
burner  fan  is  cut  off  by  the  safety 
temperature  limiter.  Restarting  requires 
resetting the limiter. To do this, unscrew the 
nut  (1)  covering  the  reset  button  (2)  and 
press the button. 

 

Resetting the STB temperature limiter: 1 - cover nut, 2 - 
reset button. 

 
The  button  can  be  pressed  only  after  the 
furnance  temperature  drops  below  95  °  C. 
The  fan  and  fuel  feeder  power  will  be 
restored. 
If  the  regulator  is  not  factory-equipped  with 
a  safety  temperature  limiter,  it  should  be 
connected  to  the  regulator  terminals  1-2  as 
an external device.  

 

The  safety  temperature  limiter 
must  have  a  rated  operating 
voltage  of  at  least  ~  230  V  and 
should 

have 

the 

applicable 

approvals. 

 

Dangerous  voltage  is  present  on 
terminals 1-2. 

If the STB is not installed on terminals 1-2 of 
the  regulator, a bridge  must be used, which 
should be made with an insulated wire with a 
cross-section  of  at  least  0.75  mm2,  with 
insulation  thick  enough  to  meet  the  safety 
requirements for the boiler. 

 

The regulations require the use of 
the STB limiter. 

5.10

 

Connecting the room panel 

The maximum length of the wires connecting 
the room panel (room thermostats) with the 
regulator  should  not  exceed  30  m.  This 
length  can  be  longer,  when  wires  with  a 
cross-section greater than the recommended 
0.5 mm2 are used. 

 

Przekrój przewodów 12 V oraz GND 
do  podłączenia  panelu  pokojowego 
powinien  wynosić  co  najmniej  0,5 
mm

2

.  

• Four-wire connection 

Connect according to the electric diagram. 
 

• Two-wire connection 

Two-wire  connection  requires  a  5…  12  VDC 
power supply with a minimum current of 200 
mA.  Power  supply  points:  GND  and  VCC 
connect  to  an  external  power  supply,  which 
is  not  a  standard  regulator  equipment. 
Connect  the  D  +  and  D-  lines  as  shown  in 
the 

electric 

diagram.

Summary of Contents for ecoMAX920 P1-CH

Page 1: ...coMAX920P1 CH FOR BLOWING TYPE BOILER FOR SOLID FUEL I OPERATING AND INSTALLATION MANUAL ISSUE 1 0 09 2020 the device is not a standard equipment of the regulator ecoNET300 ecoNET apk ecoNET app www e...

Page 2: ...ction of the wires may damage the regulator The controller cannot be used in conditions of water vapor condensation and exposed to water MAIN PRINCIPLES OF PROPER FUZZY LOGIC FURNISHING The controller...

Page 3: ...MENTS 12 3 INSTALLATION OF THE CONTROL PANEL 12 4 WORKING MODULE INSTALLATION 12 5 IP PROTECTION RATE 12 6 ELECTRICAL CONNECTION 19 12 7 ELECTRICAL SCHEME 22 12 8 CONNECTION OF TEMPERATURE SENSORS 12...

Page 4: ...rinsically safe device ie in a failure condition it can be a source of a spark or high temperature which in the presence of flammable dusts or gases may cause a fire or explosion The surroundings of t...

Page 5: ...ept no liability for damage caused by failure to follow the instructions 4 Record keeping Please keep this installation and operating manual and all other applicable documentation carefully so that yo...

Page 6: ...Manual ecoMAX920P1 CH...

Page 7: ...FL Feeder Feeder efficiency Feeder efficiency time Efficiency feeder time Fuel weight Filling the feeder Regulation mode Standard Fuzzy Logic Fuel Level Alarm level Fuel Level calibration Cleaning Bur...

Page 8: ...econd method to turn on the stove Press the menu button and then press the button To turn off the stove press the menu button and then press button then the stove will go into the extinguishing proces...

Page 9: ...which translates into the actual burner power level The parameters of the burner power levels are available in the menu Furnance settings Power modulation The controller decides about the power of th...

Page 10: ...this will increase the temperature of the burner The parameters of the SUPERVISION mode must be selected so that the burner temperature in this mode gradually drops Incorrect settings can lead to over...

Page 11: ...ature Thanks to this when selecting a heating curve appropriate for a given building the room temperature heating zone will remain approximately constant regardless of the outside temperature Heating...

Page 12: ...ek in the Schedule setting Fuel level configuration Activation of the fuel level indicator To enable display of the fuel level set the parameter value Stove settings Fuel level Alarm level to a value...

Page 13: ...nd from the next room panel it closes the SP2 damper and then another SP3 damper If all the room panels report no heat demand in all heating zones the stove switches to the BURNING OFF mode and then t...

Page 14: ...14 ecoNET app...

Page 15: ...15...

Page 16: ...16 INSTALLATION MANUAL AND SERVICE SETTINGS ecoMAX920P1 CH...

Page 17: ...temperature sensor 5 supply temperature sensor 6 exhaust fan 7 burner fan and burner feeder 8 air damper actuator 9 room panel with a room thermostat function 10 external air intake 11 air supply duc...

Page 18: ...ions of wheel transport IP protection class The casing of the regulator provides IP20 protection The casing on the side of the terminal cover has the IP00 protection degree therefore the terminals mus...

Page 19: ...onnected to it You should remember about the safety rules related to electric shock The regulator must be equipped with a set of plugs inserted into the connectors for supplying 230V devices With a me...

Page 20: ...d cable 5 cable clamp 6 connector Separate electrical wiring from hot stove components especially flue pipes After connecting the wires it is absolutely necessary to put the cover back in its place Al...

Page 21: ...stat function HS heater exchanger temperature sensor CT4 ES type supply temperature sensor type CT4 FS exhaust gas temperature sensor type CT2 S FOS feeder temperature sensor type CT4 T thermostat int...

Page 22: ...all of the building usually it is the northern side in a roofed place The sensor should not be exposed to direct sunlight and rain Install the sensor at a height of at least 2 m above the ground away...

Page 23: ...T6 P weather External Temp C Min Nom Max 25 901 6 901 9 902 2 20 921 3 921 6 921 9 10 960 6 960 9 961 2 0 999 7 1000 0 1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8 1...

Page 24: ...iler it will supply 12V DC to terminals 43 44 After the furnace temperature drops below the parameter Reserve boiler activation temperature the regulator will stop supplying voltage to contacts 43 44...

Page 25: ...vice The safety temperature limiter must have a rated operating voltage of at least 230 V and should have the applicable approvals Dangerous voltage is present on terminals 1 2 If the STB is not insta...

Page 26: ...eration detection Fan speed multipier Burning off Max time of burning off Min time of burning off Blowing power Blowing time Blowing pause Blowing start Blowing stop Cleaning Cleaning time firing up C...

Page 27: ...eration time with minimum power after firing up The power is determined by the parameter Minimum power airflow job Thermostat mode Switches the burner into Thermostat mode where the burner works with...

Page 28: ...llows you to burn the fuel supplied in Supervision with low emissions Minimum blowing power Minimal power of the burner blower fan that can be selected by the user of the regulator It is only used to...

Page 29: ...rs Log out Restoring the service settings will also restore the settings from the main user menu Exit H Selecting Yes saves all service settings after changing parameters in the service menu Touch pan...

Page 30: ...ering up the regulator Checking the temperature sensor is described in point 12 11 6 4 Unsuccessful firing up attempt The alarm will occur after the third unsuccessful attempt to automatically fire up...

Page 31: ...nents 7 2 Replacing the mains fuse The mains fuse is located inside the controller housing The fuse may only be replaced by a suitably qualified person after disconnecting the mains supply Use time de...

Page 32: ...manually the limiter should be unlocked point Check the burner fan and replace if necessary The exhaust fan is not working Check if the mains fuse of the exhaust fan is not blown and replace if neces...

Page 33: ...33...

Page 34: ...34 ul Obornicka 71 62 002 Suchy Las Polska Tel 61 811 70 37 biuro kipi pl www kipi pl BDO 000179569...

Reviews: