Connecting the exhaust gas temperature sensor: 1 -
exhaust gas temperature sensor, CT2S type, 2 - sensor
lead, 3 - flue.
Opening the furnace door may
cause the exhaust gas temperature
to
rise
above
the
thermal
resistance of the sensor, it may
burn out the sensor.
5.5
Checking temperature sensors
Temperature sensors can be checked by
measuring their resistance at a given
temperature.
In
case
of
significant
differences between the measured resistance
value and the values from the table below,
the sensor should be replaced.
A very accurate multimeter should be used
to check the CT2S sensor, otherwise the
sensor can only be checked roughly.
CT4
External
Temp.
°C
Min.
Ω
Nom.
Ω
Max.
Ω
0
802
815
828
10
874
886
898
20
950
961
972
25
990
1000
1010
30
1029
1040
1051
40
1108
1122
1136
50
1192
1209
1225
60
1278
1299
1319
70
1369
1392
1416
80
1462
1490
1518
90
1559
1591
1623
100
1659
1696
1733
CT6-P (weather)
External
Temp. °C
Min.
Ω
Nom.
Ω
Max.
Ω
-25
901,6
901,9
902,2
-20
921,3
921,6
921,9
-10
960,6
960,9
961,2
0
999,7
1000,0
1000,3
25
1096,9
1097,3
1097,7
50
1193,4
1194,0
1194,6
100
1384,2
1385,0
1385,8
125
1478,5
1479,4
1480,3
150
1572,0
1573,1
1574,2
CT2S-2
(fumes)
Temp.
°C
Min.
Ω
Nom.
Ω
Max.
Ω
0
999,7
1000,0
1000,3
25
1096,9
1097,3
1097,7
50
1193,4
1194,0
1194,6
100
1384,2
1385,0
1385,8
125
1478,5
1479,4
1480,3
150
1572,0
1573,1
1574,2
5.6
Connecting the optical sensor
Optical sensor asking according to the
diagram with the polarity of the SYG (+) and
GND (-) invitation. Reading the indications
from the optical flame system is in the menu
item:
Information
→
Flame
Incorrect connection of the optical
sensor
will
not
damage
the
regulator or the sensor itself, but
the burner flame detection will be
incorrect.
5.7
Connecting a reserve boiler
The regulator can control the operation of a
reserve boiler (gas or oil). Connection to a
reserve boiler should be made by a qualified
installer, in accordance with the technical
documentation of this boiler. The reserve
boiler should be connected via a relay to
220ºC