General Vent Installation Information
This gas appliance is approved to be vented either through the side wall
or vertically through the roof. Only Kingsman Flex(Z-Flex)Venting Kits
and components specifically approved and LABELED for this stove
FRAMING DIMENSION
Combustible Wall
may be used. This appliance is also approved for use with Simpson- Cut a 11” hole through exterior wall and frame as shown below.
Duravent Direct Vent system, Ameri-Vent Direct Vent Pipe System, ICC
Non combustible Wall
Excel Direct, Metal Fab Sure-Seal DV and Selkirk Direct Temp.
Cut or drill 8” or 204mm diameter hole.
RIGID OR HARD PIPE
When using Simpson Duravent, AmeriVent pipe, ICC Excel Direct, Metal Fab
Sure-Seal DV and or Selkirk Direct Temp a Duravent hardpipe adapter must
be used (part # ZDVDFA for fireplaces and part # ZDVDKA for Stoves,
FIGURE 1
SEAL WITH HIGH TEMP. SEALANT
Serenity and ZDV3624B). Follow installation instructions provided by Simpson
Duravent/AmeriVent/Selkirk Direct Temp, ICC Excel Direct, Metal Fab Sure-
Seal DV for installation of pipe and adhere to the clearance to combustibles
provided in this manual. Apply a bead of Mill Pac high temp sealant to all joints
of pipes, adapters and termination, when using Kingsman Flex(Z-Flex)Venting
venting and Simpson Duravent venting.
NOTE: Increase framing depth by one inch when using hardpipe.
MAX. DISTANCE BETWEEN SPACERS 2 FEET
SPRING SPACERS
OPTIONAL
CLAMPS
Flex Pipe Venting
Flex pipe is shipped in unexpanded length. When installing pipe expand
the lengths. Pipe can be expanded to twice their lengths e.g. 4ft. to 8ft.
Do not use more than 2 couplers to extend short pipes. Single sections
OPTIONAL
CLAMPS
SEAL WITH HIGH TEMP. SEALANT
are preferred in an installation attaching at the fireplace and termina-
tion.
Place the spring spaces provided approximately every two feet to stabi-
lize 4” flex in the center of 7” flex. When forming bends place spring in
bend or before and after. (See Fig. 1).
NOTE: It is critical to the proper and safe operation of this fireplace
that on all connections the inner liner and the outer casing are both
caulked with liberal amounts of sealant. Do not use any kind of tape
or silicone other than that recommended in this manual. Mill Pac
Sealant
Horizontal runs require support metal straps every 2 feet. In off set installation support straps should be used to stabilize pipe.
Expand 4” and 7” flex pipe to the point that the 7” protrudes approximately 2 to 3 inches past outer wall and the 4” flex protrudes approxi-
mately 2 to 3 inches past the 7” flex. See Fig. 1. Attach the 4” pipe to the termination first and secure with sealant and 4 screws, then
attach the 7” flex to the termination with sealant and 4 screws. Termination may then be moved back to the outer wall and attached to
home by screwing into the framing. Silicone around termination to waterproof. If siding shield is going to be used attach this using same
attaching hole as the top of termination after termination has been caulked for water proofing.
Use Term Hi Temp Sealant
Apply a bead of mill pac high temp sealant to all joints and secure with 4 screws at every connection provided at fireplace, termination
and any joint if joining any sections of pipe.
WARNING: DO NOT mix parts from different systems unless stated in the manual.
WARNING:
WHEN THE HORIZONTAL VENT TERMINATION IS ACCESSIBLE A CERTIFIED GUARD
(SAFETY CAGE) SHALL BE INSTALLED.
49
Summary of Contents for MDV31
Page 41: ...Gas Conversion for Modulator PART C WARNING WARNING 41...
Page 44: ...Configuration 1 Basic manual HI LO and manual ON OFF capabilities 44...
Page 45: ...Receiver Module 584 523 521 221 1001 P221SI Receiver Module 584 523 521 221 1001 P221SI 45...
Page 46: ...Receiver Module 584 523 521 221 1001 P221SI Receiver Module 584 523 521 221 1001 P221SI 46...
Page 54: ...For Models MDV31 39 Replacement Parts continued 54...