MQZCV34BG Framing Dimensions- Recessed Front Chase with Front Grill
Grill
MUST
be located at top of chase.
V34EG
Front Grill must be used. No Side Grill Option as Chase is too small.
NOTE: These structures are not load bearing.
Framing for Horizontal Vent
Termination
(See
Installation of Side
Wall Venting
Section)
No loose Combustibles (wood, wiring, etc.) are allowed inside the
open Chase area.
RIGHT SIDE
Note Orientation of
2x4’s. This will provide
the correct opening
width for Front Grill.
Unit and Framing
can be covered
with a combustible
i.e., drywall.
8” MIN from top of pipe
to enclosure top.
No Crossmember
at front of Chase
Front Grill Opening
3-
1/4” x 31-3/8”
Sealed Top of
Chase
Max 4-
1/4” to back
of chase
Sealed Top of
Chase
Front Grill
Required
Optional Additional
Rear Grill- Must be in
the same Pressure
Zone (Room / Area)
16