1- PRODUCT DESCRIPTION 

The control unit has been designed to manage 1 or 2 230 Vac motors gate automations. 

To start the system it is necessary to: 

1- Connect the power supply, the motors, and the accessories as indicated in the 2nd paragraph 

2- Set the dip-switches (paragraph 4A) and the trimmers (paragraph 4B) depending on the wanted functioning and on the 

conditions of the system. 

3- Perform the standard programming procedure (paragraph 6B) or the professional programming procedure (paragraph 6D), to 

recognize the starting point and the end point of the travel. 

4- Perform the checks reported on paragraph 6C (warning before starting). 

 
      If the control unit keeps on having problems after these steps, see paragraph 9 “Signaling led”, to identify possible 

anomalies, and paragraph 14 “inconvenient and remedy” to try to eliminate them. 

1B - STARTING MODALITY 

- Management and control for 1 or 2 230Vac motors (terminals 30,31,32,33,34,35).

- Double opening-closing limit switch inputs (terminals 4,5,6,7,8).

- 433.920Mhz rolling code built-in receiver (code: “RX STAR”, see paragraph 1A – 13B).

- Removable memory (code: “MEMO 200”) containing up to 200 memorized radio codes (paragraph 1A - 13A).

- 6 signaling led (paragraph 1A – 9).

- Predisposition for the card for electric lock control connection (max 15W, optional) (see paragraph 12D).

- Customizable and differentiable slow down in opening and closing thanks to the professional learning procedure (see paragraph 6D).

- Built-in lamp intermittent manager (see paragraph 12A).

- Customizable pedestrian opening by pedestrian programming procedure (see paragraph 7).

- Customizable delay between the wings in closing from 0 to 15 sec. by trimmer (see paragraph 4B).

- Pause time before automatic reclosing customizable from 0 to 90 sec. by trimmer (see paragraph 4B).

- Sensibility of the intervention adjustable from 0.1 to 3 sec. by trimmer (see paragraph 4B).

- Power/speed adjustable from 50% to 100% by trimmer (see paragraph 4B).

- Input for control-by-wire to manage start, stop and pedestrian opening.

- Double safety inputs: closing (terminal 13) and opening and closing (terminal 14).

- Input for warning light to signal the wings position (see paragraph 12C).

1C - MAIN FEATURES 

If you perform the standard programming procedure (see paragraph 6B), and there are no modifications on the trimmer regula-

tion (see paragraph 4B) and on dip switches (see paragraph 4A), the control unit will act as follows: 

- The safety devices in closing, connected to “PHO1” contact (terminal 13), will intervene only in closing, inverting the motion. 

- The safety devices in opening, connected to “PHO2” contact (terminal 14),

 

will intervene both in closing and in opening, 

keeping on the motion when the device has been cleared (setting by the dip 5 “PHO2”). 

- Activation of electric limit switches management (terminals 4,5,6,7,8) only if they are connected. If there are no electric limit 

switches, the terminals must be free. 

- Pause time before automatic reclosing equal to 45 seconds. 

- Pedestrian opening procedure controlled by cable and by transmittter (if the transmitter has been programmed by the  

procedure as per paragraph 3b) and with total wing opening operated by MOT1 (terminals 30,31,32). 

- The slowdowns are set to the final 15% of the travel. 

1E - PRESETS 

1A - GENERAL DESCRIPTION 

Signaling led

(Paragraph 9) 

Programming 

buttons

Dip-switch function 

setting

(Paragraph 4A-5)

Setting trimmers

(Paragraph 4b-8)

Removable 

spare fuse 

Control unit supply 

230 Vac  

Secondary 1 transformer 

12 Vac 

Primary transformer 

230 Vac 

Secondary 2 transformer 

20 Vac 

24 Vdc, max 15W, protected by fuse 

Photocells output 

230 Vac, max 25W, protected by fuse 

Flashing lamp output (Terminals 28,29) 

24 Vdc, max 3W, protected by fuse 

Open gate warning light output (Terminals 15,17) 

-20 ÷ +55 

Working temperature 

20Va 

Transformer power 

Motor output 

230 Vac (Maximum 500Watt per motor) 

1D - TECHNICAL DATA 

Summary of Contents for Star 2230

Page 1: ...Star 2230 INSTRUCTION MANUAL EN Star 2230 Control unit for 1 or 2 230Vac motors ...

Page 2: ...1 PRODUCT DESCRIPTION 1A GENERAL DESCRIPTION Signaling led Paragraph 9 Programming buttons Dip switch function setting Paragraph 4A 5 Setting trimmers Paragraph 4b 8 Removable spare fuse ...

Page 3: ... by trimmer see paragraph 4B Sensibility of the intervention adjustable from 0 1 to 3 sec by trimmer see paragraph 4B Power speed adjustable from 50 to 100 by trimmer see paragraph 4B Input for control by wire to manage start stop and pedestrian opening Double safety inputs closing terminal 13 and opening and closing terminal 14 Input for warning light to signal the wings position see paragraph 12...

Page 4: ...inals 4 6 7 8 common limit switches 7 Opening limit switch motor 2 8 Closing limit switch motor 2 9 START contact 10 Terminal 9 11 12 COMMON 11 STOP contact 12 Pedestrian opening contact PED 13 Safety devices in closing contact PHO1 14 Safety devices in opening contact PHO2 15 Terminals 16 and 17 COMMON 0V 16 PHOTOCELLS 24Vdc 17 WARNING LIGHT 24Vdc max 3W 18 Electric lock control negative positive...

Page 5: ...to be free not bridged The control unit activate the contact only if it receive signals from connected contacts If there are no connected devices on the terminal 13 normally closed input PHO1 terminal 14 normally closed input PHO2 and or terminal 11 STOP the concerning inputs must be bridged If there are connected devices on the terminal 13 normally closed input PHO1 terminal 14 normally closed in...

Page 6: ...inals 4 6 7 8 common limit switches 7 Opening limit switch motor 2 8 Closing limit switch motor 2 9 START contact 10 Terminal 9 11 12 COMMON 11 STOP contact 12 Pedestrian opening contact PED 13 Safety devices in closing contact PHO1 14 Safety devices in opening contact PHO2 15 Terminals 16 and 17 COMMON 0V 16 PHOTOCELLS 24Vdc 17 WARNING LIGHT 24Vdc max 3W 18 Electric lock control negative positive...

Page 7: ...to be free not bridged The control unit activate the contact only if it receive signals from connected contacts If there are no connected devices on the terminal 13 normally closed input PHO1 terminal 14 normally closed input PHO2 and or terminal 11 STOP the concerning inputs must be bridged If there are connected devices on the terminal 13 normally closed input PHO1 terminal 14 normally closed in...

Page 8: ... the setting of FOR trimmer power speed requires the repetition of the learning procedure point 2 because of the change of the manoeuvre time The slowdowns are automatically set in the last 15 of the travel 4B TRIMMER SETTINGS 4A DIP SWITCHES SETTINGS DIP 1 ON OFF ON OFF ON OFF FAST 2 STRIKE 3 LAMP ON OFF 4 PHO2 ON OFF 5 AUTO ON OFF 6 STEP ON OFF 7 SLOW ON OFF 8 RADIO DIP STATUS FUNCTIONING DESCRI...

Page 9: ...ocell If the PHO2 dip switch is set to OFF the safety devices in opening when they intervene invert the motion for 2 seconds and then they stop the automation So it is necessary to supply a command by wire or by transmitter to finish the travel and close the wings typical functioning of the safety edge With this setting these safety devices in closing do not intervene 5E DIP SWITCH 5 PHO2 see also...

Page 10: ...he programming procedure verify that The motors shut down a few seconds after the end of the programming procedure The control unit respond to the inputs received by wire START terminal 9 pedestrian opening terminal 12 and STOP terminal 11 The control unit respond to the inputs received by transmitter The safety devices connected to PHO1 terminal 13 intervene while the gate is closing and prevent ...

Page 11: ...mote control for the second wing 12a Choose the point of slow down with the button SET or the button 1 of the transmitter for the first wing and with the button RADIO or the button 2 of the remote control for the second wing 7 Push SET button or a button of the radio transmitter The control unit performs the opening END of learning yellow led turns off 5 The control unit perform a little opening c...

Page 12: ... a command by wire the START button or a button in the transmitter 5 The gate begins to open 6 Press the command by wire the START button or the button in the transmitter to set the widening of the pedestrian opening 1 Place the wings in closing position 2 RESET press button SET for 2 seconds the yellow led flashes 3 Press START button the yellow led stays on 4 Press button SET the yellow led flas...

Page 13: ...turning the trimmer clockwise The intervention delay can be set between 0 1 and 3 seconds Thus if the trimmer is set at the minimum then the intervention time is equal to about 0 1 seconds if adjusted to an intermediate position it is equal to about 1 5 seconds while at the maximum the intervention time will be about 3 seconds See also paragraph 11D 8C Trimmer OBS Obstacle sensitivity YELLOW LED S...

Page 14: ...closing commands neither automatic nor by wire as long as the contact will be opened again The pedestrian opening is a partial opening or total opening if the installer wants it of the wing opened by MOT1 terminals 30 31 32 To activate the pedestrian opening function it is necessary to make the pedestrian opening programming procedure see paragraph 7 The pedestrian opening can be managed by a chan...

Page 15: ...e the motors absorb more current 11D OBSTACLE DETECTION BY POWER ABSORPTION The control unit has a self test function of the safeties connected to the PHO1 and PHO2 input It switches off the transmitter to check the commutation of the corresponding receiver contact before the execution of each manoeuvre To activate this self test function proceed as follows connect the positive of the photocell tr...