181922 Rev B
6
Controlled by ECCN:EAR99
PROPRIETARY INFORMATION –
Refer to the restrictions provided on the Title Page of this document.
EAR DATA
- Subject to the export control restrictions on the Title
Page of this document or file
ALARM SILENCE switch
o
Use to silence the audible alarm
TEST/RESET switch with DELAY ENGINE STOP indicator
During normal “System OK” state:
o
Allows testing of indicators and audible alarm during standby operation
During Fire Event:
o
Illuminates solid red when fire event is detected
o
Illuminates blinking red when pressed and released for a 15 second additional delay.
o
Returns to solid red illumination after additional time delay had elapsed
o
Turns off when the shutdown signal has been activated
o
Resets protection panel when pressed and released after a fire event or significant
gas leak
Early warning signal output
Engine shutdown signal output
Manual activation switch signal input
Operating Temperature Range
-40
⁰
F to 158
⁰
F (-40
⁰
C to 70
⁰
C)
Quiescent Current
50mA (Nominal) @ 24V
Operating Voltage
9 to 32Vdc
FIGURE 2 - PROTECTION PANEL