TROUBLESHOOTING GUIDE
SYMPTOM
PROBABLE CAUSE
CORRECTIVE ACTION
All Protection Panel indicators
off.
No power to protection panel
Check protection panel fuse
(15A).
Check power and ground
connections & voltage to
protection panel.
(NOTE: Below 9 volts the
system will not function.)
If the power (~24Volts) and
ground are present at the
protection panel, replace it.
Protection Panel green
SYSTEM OK indicator
blinking.
Low battery voltage
Check connections & voltage
to system.
Below 22 volts the system will
provide low voltage indication.
Protection Panel green
SYSTEM OK indicator off,
yellow fire TROUBLE
indicator on, red fire ALARM
indicator on solid and audible
alarm on.
System automatically
discharged
Correct the cause of the
system activation and reset
the system as described in
the system reset portion of
this manual
Protection Panel green
SYSTEM OK indicator off,
yellow fire TROUBLE
indicator on, red fire ALARM
indicator on blinking and
audible alarm on.
System manually discharged
Correct the cause of system
activation and reset the
system as described in the
system reset portion of this
manual