SYMPTOM
PROBABLE CAUSE
CORRECTIVE ACTION
Component not connected or
damaged harness in gas
detection circuit
Check gas detectors’ LED
indicators. If any are not
illuminated this is an
indication that power is not
being received.
Check harness connections at
the gas detectors.
Check for the correct voltage
values on the gas circuit. (Pin
A: 22-26 volts, Pin B: Ground,
Pin C: 11-15 volts).
NOTE: The gas detectors will
not be powered if Pin B is not
equal to Ground.
If the voltage at Pin A or C is
low, use an EOL and starting
at the first connection in the
gas circuit systematically
check the voltage at each
connection until the section
where the fault exists is
identified.
Protection Panel green
SYSTEM OK indicator on
solid, red gas LEAK indicator
blinking.
Trace gas leak present
Correct the cause of the leak.
System will reset itself when
trace gas leak dissipates
below detection threshold.
Protection Panel green
SYSTEM OK indicator on
solid, red gas “LEAK”
indicator on solid and audible
alarm on.
Significant gas leak alarm has
occurred and may or may not
still be present.
Locate gas sensor that
initiated alarm by checking
sensor status indicators.
Correct the cause of the leak.
Reset system as described in
the system reset portion of
this manual and monitor for
alarm.
Status indicator on gas sensor
blinking green
Power up period
Allow 30 seconds after power-
up for indicator to turn solid
green