5
2. Product summary and explanation
2.1 Product summary
EZYPAT / / SMARTPAT (Tester) is a hand-held portable appliance
tester and can test electrical safety of Class I
and Class II appliances. The
Tester performs test and indicates PASS/ FAIL result complying with the
criteria of judgement defined in T
he IEE Code of Practice for In-service
Inspection and Testing of Electrical Equipment: 2003.
As a guide, the IEC standard defines these two categories as follows:
Class I : Appliances which have a functional insulation throughout and an earth
connected case. These are often described as earthed appliances.
Class II : Appliances which have both functional and additional insulation where
any metal parts cannot become
“Live” under fault conditions.
2.2 Test Function
Available functions vary depending on models.
Function
EZYPAT
SMARTPAT
C
L
1
Protective
conductor
resistance
test
(Test
current
200mA
DC
nominal)
レ
レ
レ
C
L
2
Insulation test (250V or
500V)
レ
レ
レ
Substitute leakage
current test
レ
レ
レ
Run leakage current test
レ
レ
Load current
レ
レ
Extension Lead test
レ
レ
レ
RCD Test
レ
Remote function
レ
2.3 Features
Check for whether the appliance is switched ON.
Selection for 250V or 500V on the insulation resistance test.
Null function for the protective conductor resistance test.
Auto-testing & PASS/ FAIL indication with backlight
Auto-power-off
Remote testing (SMARTPAT only)