14
3.2 General specification
Reference conditions
Specifications
are
based
on
the
following conditions, except
where
otherwise stated:-
(1) Ambient temperature: 23±5˚C
(2) Relative humidity: 45 - 75%
(3) Attitude: Horizontal
(4) AC power supply: 230 V, 50Hz
(,SMARTPAT)
(5) Altitude: 2000m or less
Battery type
Six size AA alkaline batteries (LR6)
Operating temperature and
humidity range
0ºC to +40ºC, relative humidity: 85% or
less (no condensation)
Storage temperature and
humidity range
-20ºC to +60ºC, relative humidity: 85%
or less (no condensation)
Rate voltage and frequency
(, SMARTPAT)
Rated voltage: 230 V +10%, -15%
Rated frequency: 50 Hz
Maximum load current at test
socket (, SMARTPAT)
3 kVA (15sec.)
Outer dimension and weight
Outer dimension:
261(L) × 104 (W) × 57(D)mm
Weight (Tester body only):
EZYPAT: Approx. 860g
: Approx. 950g
SMARTPAT:Approx. 970g
Auto power off
The Tester turns off automatically after 5
minutes.
Applicable standards:
Instrument operation
The IEE Code of Practice for In-service
Inspection and Testing of Electrical
Equipment
Safety
IEC/EN61010-1 CAT II 300V-instrument
IEC/EN61010-2-030
IEC/EN61010-031
CAT
III
600V
(MODEL7208 / MODEL7168 )
EMC
EN61326-1, 2-2
Possible number of measure-
ments where battery voltage is
Approx. 1400 times
(CLI