PRE-INSTALLATION
Note:
-
Each run of product must be connected to a Ketra N3 Satellite.
-
The N3 Satellite is installed in line between the AC Mains power source and the run of G2 Linear. It
couples together power and data, enabling a simple installation using a single class 1 cable run. The leader
cable is 50 ft (15.24 m) long and may be cut to length. The products do not require a separate low-voltage
data cable.
-
Please refer to the installation instructions for the N3 Satellite for more details.
-
Each N3 Satellite can support up to 40 ft (12.19 m) of product. For longer run lengths, use additional
-
N3 Satellites for each 40 ft (12.19 m) (or less) of product.
-
N3 Satellites can be connected to the same power source and do not each require a dedicated circuit.
-
Connect all product in a single run from the N3 Satellite.
-
‘Home Run’ style installations are not supported.
Home run topologies
are not supported
100-277 VAC
50/60 Hz
Mains Supply
100-277 VAC
50/60 Hz
Mains Supply
G2
N3 Satellite
N3 Satellite
N3 Satellite
G2
G2
G2
fig. 2
fig. 3
G2
G2
G2
G2