5. Fault detection Standard control unit

Power-LED lit
Alarm LED flashing
Flap-LED flashing,
Acoustic signal

Power-LED lit,
Alarm-LED flashing,
Backwater-LED flas-
hing 
Flap-LED flashing,
acoustic signal

Flap cannot be closed com-
pletely during start-up or by
the “test” key, i.e. the flap is
blocked  by  an  object  in  the
backwater flap
“Flap fault”
- Wrong lever position during
cover fitting

- Backwater detected.
The  flap  cannot  be  closed
completely, however, i.e. it is
blocked by an object
“Flap fault during backwater”

Remove the mains plug, deactivate
the battery, open the Staufix cover,
eliminate the blockage and return to
operation

Recommendation:
Inform a specialist company

See  installation  instructions  010-
842 (section 4.2.1)

Close  the  emergency  valve.  After
the  end  of  backwater,  remove  the
blockage as described

Caution:  Check  position  of  the
operating  valve! 

The  control  at-

tempts to close the flap 3 x in the
interval and perhaps eliminate the
blocking  object  in  the  process.  If
the object can be removed by the
flap  movement  during  these  cy-
cles,  the  system  is  ready  to  be
used again. If this does not work,
the system switches to fault. Ack-
nowledgement of the acoustic sig-
nal is possible. It is also possible to
remove the object by flushing the
line. This can be checked by pres-
sing the test key again. In the event
of a negative result, the fault mes-
sage  appears  again;  the  object
must  be  removed  as  described
under remedial measures.

The KESSEL control unit detects faults during start-up and during operation, allowing them to be remedied easily.

5.1 Problems with mains operation:

Fault display

Cause

Remedy

Notes

Power-LED flashing,
alarm-LED flashing
Acoustic signal

Power-LED lit,
alarm-LED flashing
quickly
Flap-LED flashing {} 
Acoustic signal

Power-LED lit,
alarm-LED flashing
quickly
Backwater-LED flas-
hing
Acoustic signal

Battery is missing or faulty
“Battery fault”

- Initialisation: 

“Motor” con-

trol  cable  is  not  connected,
connected with inverse pola-
rity or is broken

During operation:

“motor”

control cable faulty
“Motor fault”

-  Initialisation:  “Probe”

control cable is not connec-
ted,  connected  with  inverse
polarity or is broken

- During operation:

“Probe”

control cable faulty
“Probe faulty”

Remove  the  mains  plug,  connect
batteries, replace by new batteries
if necessary
When the unit is ready to function,
a running light appears on the dis-
play again.

Remove  the  mains  plug,  dis-
connect the battery; check the con-
trol cable for correct connection or
passage,  replace  motor  if  neces-
sary.

Remove the mains plug, deactivate
the battery; check the control cable
for correct connection or passage,
replace probe if necessary.

- Initialisation: T

he system can be

put into operation, i.e. it is functional.
Alarm can be acknowledged.

- Operation: 

The fault message ap-

pears after a maximum of 5 minutes.
The  system  is  ready  for  operation,
manual mode is possible.

Fault detection only takes place du-
ring operation (see  8.2 “Add.funct”).

- Initialisation:

Cannot be put into

operation

- During operation:

Fault detection

during  manual  operation  test
cycle/backwater
The  probe  is  scanned  every  2  se-
conds.

Power-LED lit 
Alarm LED flashing
alternating with 
flap-LED

Max. number of cycles
for flap exceeded

Motor transmitting figure 
exceeded

Replace motor

Inform the customer service
partner

Motor service life reached

Flap closes too often within a short
time

Power-LED lit 
Alarm LED flashing
at the same time as 
Flap LED

010-845EN_FKA_Schaltgerät_2011_03_010-131 Stand 10-07_AKTUELL2008.qxd  25.10.11  10:32  Seite 8

Summary of Contents for Staufix FKA Comfort

Page 1: ...em Fachbetrieb Inbetriebnahme Einweisung Techn nderungen vorbehalten Schaltger t Spritzwassergesch tzt IP 54 Steckeranschl sse f r einfachste Montage Kein ffnen zur Installation erforderlich Kein ffne...

Page 2: ...EN 13564 Seite 10 6 3 Pr fung der optischen Sonde Seite 10 7 Betrieb Komfort Schaltger t 7 1 Betriebsf lle Diodenanzeige Seite 11 7 2 Funktionstasten Ger t Seite 11 7 3 Ausserbetriebnahme Seite 11 7 4...

Page 3: ...rokabel sowie alle anderen elektrischen Anlagenteile in einem einwandfreien Zu stand be nden Bei Besch digung darf die Anlage auf keinen Fall in Betrieb ge nommen werden bzw ist umgehend ab zustellen...

Page 4: ...erlegen Anschlie end am Schaltger t den Motorstecker grau Bild1 und den Sensorstecker wei Bild 2 entsprechende den Markierungen Bild 3 aufstecken und handfest verschrauben 1 Nm Bitte beachten Stecker...

Page 5: ...entrale Leittechnik des Geb udes angeschlossen werden An schluss siehe Beiblatt potentialfreier Kon takt Jeder Alarm wird bei R ckstau oder einer St rung ber den potentialfreien Kontakt gemeldet Bei K...

Page 6: ...ste a b c d e f g h i j k l 3 2 Funktionspr fung nach DIN EN 13564 Verschluss schraube R1 2 Betriebsverschluss 4 mittels Pr ftaste schlie en Den Notverschluss 3 mit dem Handhebel verschlie en Die Vers...

Page 7: ...ftaste TEST Der Betriebsverschluss kann z B f r die Wartung manuell bet tigt werden Durch einmaliges Dr cken wird die Klappe ge schlossen Durch nochmaliges Dr cken wird die Klappe wieder ge ffnet Das...

Page 8: ...kannt und somit leicht abgestellt werden 5 1 St rungen bei Netzbetrieb Fehleranzeige Ursache Abstellma nahme Hinweise Power LED blinkt Alarm LED blinkt Signalton Power LED leuchtet Alarm LED blinkt sc...

Page 9: ...st 2 Stunden funktions f hig Anschlie end geht das Ger t in den Sleep Modus siehe Kap 6 3 Zusatzfunktionen Fehlererkennung erfolgt nur im Be trieb Die Abfrage der Sondenleitung er folgt alle 60 sec 5...

Page 10: ...r Displayanzeige a b c d e f g h i j k m l 6 2 Funktionspr fung nach DIN EN13564 Verschluss schraube R1 2 Betriebsverschluss 4 mittels Pr ftaste schlie en Den Notverschluss 3 mit dem Handhebel verschl...

Page 11: ...te TEST Der Betriebsverschluss kann z B f r die Wartung manuell bet tigt werden Durch einmaliges Dr cken wird die Klappe ge schlossen Durch nochmaliges Dr cken wird die Klappe wieder ge ffnet Das Schl...

Page 12: ...Displayaufbau Das Steuerger t l sst sich intuitiv mit Hilfe der Men tasten bedienen Das Displaymen ist in drei Ebenen aufgeteilt z B 1 Hauptmen 1 1 Untermen 1 1 1 Zweite Untermen ebene 1 1 1 Wertanze...

Page 13: ...Logbuch 1 3 Steuerungstyp 1 4 Wartungstermin 1 5 Parameter Displayanzeige Beschreibung Information Durch Dr cken von OK wird die entsprechende Zeit Anzahl ange zeigt 1 1 1 Gesamtlaufzeit 1 1 2 R ckst...

Page 14: ...erschrieben Ger tespezifikation wird angezeigt Hardware und Softwareanzeige Mit OK wird der letzte Wartungs termin angezeigt 7 Betrieb Komfort Schaltger t Mit OK wird der n chste Wartungs termin angez...

Page 15: ...erz gerung nach Stromausfall Defaultwert sind 2 sec Nicht belegt Nicht belegt Displayanzeige Beschreibung Information Die Einschaltverz gerung Motorklappe wird angezeigt Defaultwert sind 2 sec nicht b...

Page 16: ...nd Uhrzeit ein gestellt wertden Siehe 7 4 1 Erstinbetriebnahme Hier kann eine Men sprache ausge w hlt werden Siehe 7 4 1 Erstinbetriebnahme 7 Betrieb Komfort Schaltger t Hier kann der Displaykontrast...

Page 17: ...nd somit leicht abgestellt werden 8 1 St rungen bei Netzbetrieb Diodenanzeige Fehleranzeige Ursache Abstellma nahme Hinweise Power LED blinkt Alarm LED blinkt Signalton Power LED leuchtet Alarm LED bl...

Page 18: ...ermeldung erneut auf der Gegen stand ist wie unter Abstellma nahme be schrieben zu beseitigen Displayanzeige Ursache Abstellma nahme Hinweise Batterie fehlt oder ist defekt Batteriefehler Initialisier...

Page 19: ...t das Ger t in den Sleep Modus siehe Kap 6 3 Zusatzfunktionen Fehlererkennung erfolgt nur im Be trieb Die Abfrage der Sondenleitung er folgt alle 60 sec Alarm LED blinkt schnell R ckstau LED s blinkt...

Page 20: ...Funktion wird verhindert dass die Batterien v llig entleert werden und dann bei Stromausfall nicht mehr funktionsf hig sind Beispielsweise wenn die Steuerung w hrend der Bauphase installiert wird aber...

Page 21: ...nleitun gen und den g ltigen Normen 2 KESSEL stellt ausdr cklich klar dass Ver schlei kein Mangel ist Gleiches gilt f r Fehler die aufgrund mangelhafter Wartung auftreten Hinweis Das ffnen von versieg...

Page 22: ...22 Notizen...

Page 23: ...23 Notizen...

Page 24: ...a Sanit rfirma Elektrofirma Adresse Telefon Telefax Abnahmeberechtigter Adresse Telefon Telefax bergabeperson Sonstige Anmerkungen Die aufgef hrte Inbetriebnahme und Einweisung wurde im Beisein des Ab...

Page 25: ......

Page 26: ...____________ __________________________________________________________________________________________________________ Die Inbetriebnahme und Einweisung wird durchgef hrt durch Firma Adresse Ansprech...

Page 27: ......

Page 28: ...R ckstauverschl sse K Hebeanlagen K Abl ufe Duschrinnen K Abscheider Fettabscheider l Benzin Koaleszenzabscheider St rkeabscheider Sinkstoffabscheider K Kleinkl ranlagen K Sch chte K Regenwassernutzun...

Page 29: ...Commissioning Training Subject to technical amendments Control unit splashwater proof IP 54 Plug connections for very straightforward installation Does not have to be opened for installation Does not...

Page 30: ...test according to DIN EN 13564 Page 38 6 3 Testing the optical probe Page 38 7 Operating the Komfort control unit 7 1 Working conditions diode display Page 39 7 2 Device function keys Page 39 7 3 Put...

Page 31: ...case of damage the system may on no account be put into operation or must be stopped immediately Conversions or changes to the system may only be carried out in agreement with the manufacturer For saf...

Page 32: ...the motor plug grey Fig 1 and the sensor plug white Fig 2 in the control unit according to the markings Fig 3 and tighten them by hand 1 Nm Please note Grey plug to grey socket White plug to white soc...

Page 33: ...chnology of the building For connection see the leaflet on potential free contact In the event of backwater or a problem every alarm is sent via the potential free contact During flap test key functio...

Page 34: ...j Connection optical probe white k Alarm key l Test key a b c d e f g h i j k l 3 2 Functional test according to DIN EN 13564 Screwed sealing plug R1 2 Use the test key to close the operating valve 4...

Page 35: ...be actuated ma nually e g for maintenance purposes The flap is closed by pressing it once The flap is opened again if pressed a se cond time Closing and opening of the flap is indica ted by flashing...

Page 36: ...rm LED flashing Acoustic signal Power LED lit alarm LED flashing quickly Flap LED flashing Acoustic signal Power LED lit alarm LED flashing quickly Backwater LED flas hing Acoustic signal Battery is m...

Page 37: ...n the Staufix cover eliminate the blockage and return to operation The system is functional for 2 hours Then the device switches to sleep mode see chapter 6 3 Additional functions Fault detection only...

Page 38: ...keys for display a b c d e f g h i j k m l 6 2 Functional test in accordance with DIN EN 13564 Screwed sealing plug R1 2 Use the testing key to close the operating valve 4 Close the emergency valve 3...

Page 39: ...the backwater LED flashing as soon as the flap has been closed completely In addition an alarm is sounded During backwater the flap can not be opened manually Caution The end of the backwater is indi...

Page 40: ...sub menu OK is used to confirm entry or move to the next sub level of the menu ESC is used to leave the current menu level and move to the next higher level The arrow keys are used to move within a me...

Page 41: ...n The respective time number is dis played when OK is pressed 1 1 1 Overall running time 1 1 2 Backwater time 1 1 3 Number of backwater occurrences 1 1 4 Switching cycles flap 1 1 1 5 Switching cycles...

Page 42: ...last maintenance date is display ed when OK is pressed 7 Operating the Comfort control unit The next maintenance date is dis played when OK is pressed Servicing every six months is prescribed All flap...

Page 43: ...is 2 sec Not occupied not occupied Display Description Information Switch on delay for the motor driven flap is displayed Default value is 2 sec not occupied not occupied The maximum flap cycles are d...

Page 44: ...enu language can be selected here See 7 4 1 Initial operation 7 Operating the Comfort control unit The display contrast can be set here Setting range 5 20 Default value is 14 The maximum number of mot...

Page 45: ...arm LED flashing Acoustic signal Power LED lit alarm LED flashing quickly Flap LED flashing Acoustic signal Power LED lit alarm LED flashing quickly Backwater LED flas hing Acoustic signal Battery is...

Page 46: ...sage replace motor if necessary Remove the mains plug deac tivate the battery check the con trol cable for correct connection or passage replace probe if ne cessary Initialisation The system can be pu...

Page 47: ...s to sleep mode see chapter 6 3 Additional functions Fault detection only takes place on the company premises The probe is scanned every 60 se conds Alarm LED flashing quickly Backwater LED flashing q...

Page 48: ...letely and then no longer being able to function in the event of a power failure Thisisparticularlyimportantduringthe construction phase for example when the control unit is installed but not yet cont...

Page 49: ...ted in accordance with the valid installation and user s manual as well as the corresponding norms regulations 2 Wear and tear on a product will not be considered a defect Problems with pro ducts resu...

Page 50: ...50 Notice 010 845EN_FKA_Schaltger t_2011_03_010 131 Stand 10 07_AKTUELL2008 qxd 25 10 11 10 32 Seite 22...

Page 51: ...51 Notice 010 845EN_FKA_Schaltger t_2011_03_010 131 Stand 10 07_AKTUELL2008 qxd 25 10 11 10 32 Seite 23...

Page 52: ..._______________________________ Address __________________________________________________________ Telephone Fax __________________________________________________________ KESSEL Commissions no System...

Page 53: ...010 845EN_FKA_Schaltger t_2011_03_010 131 Stand 10 07_AKTUELL2008 qxd 25 10 11 10 32 Seite 25...

Page 54: ...ration and instruction were not carried out The client person responsible for initial operation was handed the following components and or product components Initial operation and instruction is being...

Page 55: ...010 845EN_FKA_Schaltger t_2011_03_010 131 Stand 10 07_AKTUELL2008 qxd 25 10 11 10 32 Seite 27...

Page 56: ...hannels K Separators Grease Separators Oil Fuel Coalescence Separators Starch Separators Sediment Separators K Septic Systems K Inspection Chambers K Rainwater Management Systems 010 845EN_FKA_Schaltg...

Page 57: ...to sono state fornite dal rivenditore specializzato Messa in funzione Istruzioni Con riserva di modifiche tecniche Centralina protetta contro gli spruzzi d acqua IP 54 Collegamenti a spina per un mont...

Page 58: ...4 Pagina 66 6 3 Controllo della sonda ottica Pagina 66 7 Funzionamento centralina Comfort 7 1 Casi d esercizio indicazione a diodi Pagina 67 7 2 Tasti di funzione apparecchio Pagina 67 7 3 Messa fuori...

Page 59: ...pianto non deve mai essere messo in funzione e deve essere spento immediatamente Trasformazioni e modi che dell impianto devono essere eseguite solo previo ac cordo con il produttore I pezzi di ricamb...

Page 60: ...to a potenziale zero In seguito fis sare alla centralina il connettore del moto re grigio ill 1 e quello del sensore bi anco ill 2 secondo i contrassegni ill 3 e avvitare a mano 1 Nm Attenzione connet...

Page 61: ...zero In caso di riflusso o guasto ogni allarme viene segnalato attraverso il con tatto a potenziale zero Durante il control lo della valvola funzione tasto Test val vola attraverso il contatto a poten...

Page 62: ...ottica bianco k Tasto allarme l Tasto Test a b c d e f g h i j k l 3 2 Controllo del funzionamento conf DIN EN 13564 Vite R1 2 Con il tasto di controllo chiudere la chiu sura d esercizio 4 Con la lev...

Page 63: ...pu essere riaperta tramite il tasto di controllo Nel funzionamento a batteria per rispar miare le batterie il tasto di controllo non pu essere attivato 4 3 Messa fuori servizio Attenzione dopo aver s...

Page 64: ...rme lampeggia Segnale acustico Power LED illumina LED allarme lampeg gia velocemente LED valvola lampeggia Segnale acustico Power LED illumina LED allarme lampeg gia velocemente LED riflusso lampeg gi...

Page 65: ...teria aprire il coperchio Staufix eli minare il blocco e mettere di nuovo in funzione l impianto L impianto pu funzionare per 2 ore Successivamente passa nella mo dalit Sleep vedi cap 6 3 Funzioni ad...

Page 66: ...o Test l Display m Tasti di funzione per display a b c d e f g h i j k m l Controllo del funzionamento conf DIN EN 13564 Vite R1 2 Con il tasto di controllo chiudere la chiu sura d esercizio 4 Con la...

Page 67: ...ra della valvola si ve rifica un riflusso esso viene segnalato dal lampeggiare del relativo LED non appena la valvola completamente chiusa Ri suona inoltre un segnale acustico Duran te il riflusso la...

Page 68: ...el display la centralina pu essere comandata intuitivamente con l aiuto dei tasti del menu Il menu del display suddiviso in tre livelli p es 1 Menu principale 1 1 Sottomenu 1 1 1 Secondo livello sotto...

Page 69: ...DisIndicazioni sul display Descrizione Indicazioni Premendo il tasto OK viene visuali zzato il relativo tempo numero 1 1 1 Tempo di funzionamento totale 1 1 2 Tempo dei riflussi 1 1 3 Numero dei rifl...

Page 70: ...gt Indicazione dell hardware e del software Mit OK wird der letzte Wartungs termin angezeigt 7 Casi d esercizio indicazione a diodi Mit OK wird der n chste Wartungs termin angezeigt E prescritta una m...

Page 71: ...i corrente Valore default 2 sec Non occupato Non occupato Indicazioni sul display Descrizione Indicazioni Viene visualizzato il ritardo d inser zione della valvola motorizzata Valore default 2 sec Non...

Page 72: ...Vedi 7 4 1 Prima messa in funzione Qui possibile selezionare una lin gua del menu Vedi 7 4 1 Prima messa in funzione 7 Casi d esercizio indicazione a diodi Qui possibile regolare il contrasto del dis...

Page 73: ...l LED di allarme lampeggia segnale acustico Power LED illumina LED di allarme lam peggia velocemente LED della valvola lampeggia Segnale acustico Power LED illumina LED di allarme lam peggia velocemen...

Page 74: ...azioni Batteria mancante o di fettosa Anomalia bat teria Inizializzazione linea di controllo Motore non collegata interrot ta o polarit invertita Durante il funziona mento linea di control lo Motore d...

Page 75: ...anto pu funzionare per 2 ore Successivamente passa nella mo dalit Sleep vedi cap 6 3 Funzioni addizionali Il riconoscimento degli errori avvie ne solo durante il funzionamento L interrogazione della l...

Page 76: ...male Questa funzione impedisce che le batterie si scarichino com pletamente e in caso di interruzione di cor rente non siano pi funzionali Per esempio se il comando viene installato durante la fase di...

Page 77: ...sorta dal relativo contratto di compravendita La constatazione di vizi evidenti deve essere comunicata tempestivamente in forma scritta in caso di presenza di difetti difficilmente visibili o impossib...

Page 78: ...78 Note...

Page 79: ...Note 79...

Page 80: ...__________________________________________________________ Telefono Fax __________________________________________________________ N commissione KESSEL Persona autorizzata alla presa in consegna _____...

Page 81: ..._________________________________________________ _______________________________________________________________________________________________________ La messa in funzione e l addestramento vengono...

Page 82: ...ollevamento K Scarichi K Separatori Separatori di grassi Separatori di coalescenza olii e benzine Separatori di amidi Separatori di sedimenti K Trattamento delle acque reflue K Pozzetti di ispezione K...

Reviews: