46/168
2016/05
TECHNICAL DATA
5.4.
Bolt connections tightening torques
Pump on pump flange
7 Nm
Level sensor and maintenance port
5 Nm
Backflow protection device (plastic)
7 Nm
5.5.
,ɈLJ[P]L]VS\TLZ
Dependence of the effective volume on intake position in approx. litres.
Effective volume in approx. litres for intake
Type
Container capacity
170[mm]
265[mm]
365[mm]
Nozzle
F XL 200
200 litres
37
85
112
120
F XL 300
300 litres
50
119
159
175
F XL 450
450 litres
63
156
216
250
Minimum activation level
The minimum height for the intake position <B> is <A>* + 5 cm.
Boring below this level is not allowed in order to prevent
the pump(s) from running dry.
* <A> = distance from container floor to pump blade wheel.
170
265
50mm
A
B
[15]
[16]