ASSEMBLY
3.2.1
Connecting the inlet
• Connect the intake pipe to nozzle <19>.
The intake can also be assembled on one of the scored
areas (see 2.5). When doing this:
• Arrange the intake above the level sensor for switching on the
pump(s). Otherwise, backflow may occur in the intake.
Alternatively, the switching points must be adjusted.
• Do not position the intake close to the level sensor, as the
sensor may be functionally compromised as a result of
contaminations and the wastewater flowing in.
If necessary, the assembly positions of the level sensor and the
maintenance port can be swapped
• Use an aligned drill bit and passage seal.
• Align the centre of the bore hole with the centre line of the sc surface
• Do not deburr the edges of the bore, as this may result in leaks.
3.2.2
Connecting the ventilation pipe
• Connect the ventilation pipe to venting connection <38>
(in accordance with DIN EN 12056-4).
It is to carry out a separate ventilation pipe at roof level.
Connections and clamps should have
noise-reduction characteristics.
[7]
[8]
19
38
Summary of Contents for Aqualift F XL Duo
Page 2: ...2 168 2016 05...
Page 26: ...26 168 2016 05 DOP 9 DOP...
Page 27: ...27 168 2016 05 DOP...
Page 30: ...30 168 2016 05...
Page 54: ...54 168 2016 05 DOP 8 DOP...
Page 55: ...55 168 2016 05 DOP...
Page 58: ...58 168 2016 05...
Page 82: ...82 168 2016 05 DOP 9 DOP...
Page 83: ...83 168 2016 05 DOP...
Page 86: ...86 168 2016 05...
Page 110: ...110 168 2016 05 DOP 9 DOP...
Page 111: ...111 168 2016 05 DOP...
Page 114: ...114 168 2016 05...
Page 138: ...138 168 2016 05 DOP 9 DOP...
Page 139: ...139 168 2016 05 DOP...
Page 142: ...142 168 2016 05...
Page 166: ...166 168 2016 05 DOP 9 DOP...
Page 167: ...167 168 2016 05 DOP...