6
228-1616 REV 7
070113
KEPCO, INC.
"
131-38 SANFORD AVENUE
"
FLUSHING, NY. 11355 U.S.A.
"
TEL (718) 461-7000
"
FAX (718) 767-1102
http://www.kepcopower.com
"
email: [email protected]
LOCAL SENSING (FACTORY DEFAULT).
Unit is shipped with local sensing jumpers installed: +S
connected to +M and –M connected to –S (see Figure 2).
FIGURE 2. KLP SERIES, REAR PANEL VIEW, JUMPERS INSTALLED FOR LOCAL SENSING
REMOTE SENSING SELECT.
First remove the factory-installed local sensing jumpers bS
and +M and between –M and –S. Then connect the +S and –S lines at the load, observing proper polar-
ity (see Figure 3). A high frequency bypass network consisting of two capacitors connected across the
error sensing point as shown in Figure 3 is recommended to reduce noise in the sense loop.
FIGURE 3. REMOTE SENSING