background image

 062119

228-1692 REV 9

9

KEPCO, INC. 



 131-38 SANFORD AVENUE 



  FLUSHING, NY. 11355 U.S.A.



  TEL (718) 461-7000



 FAX (718) 767-1102

www.kepcopower.com   



 email: [email protected]

VIII — OPERATION.

Additional features covered in the Operator Manual
are: operation via the LAN interface or analog signals
and setting coarse/fine adjustment preference of the
VOLTAGE and CURRENT controls. An Installation/
Operation Summary is also included in the Operator
Manual. The Operator Manual also covers the GPIB,
Ethernet and RS 232 interfaces, including the use of
the drivers downloadable from: 

www.kepcopower.com/drivers/drivers-dl3.htm#bop1k.

TURNING THE POWER SUPPLY ON. 

CAUTION: 

DO NOT repeatedly toggle the cir-
cuit breaker/switch as this may
damage the unit. 

Set POWER ON/OFF circuit breaker/switch on front
panel to ON. If actuator does not lock when released,
wait a few seconds before trying again. The circuit
breaker is “trip-free” design; if overload exists, contacts
cannot be held closed by actuator.

When the power supply is turned on, it per-
forms a brief self-test that includes testing the
three processors (analog, interface and dis-
play), then displays the power-up screen (see
Figure 5). If an error is detected, the FAULT
indicator will light, information about the error
will be briefly displayed on the LCD.

If the unit powers up in REMOTE mode, press

!

 to set the unit to LOCAL mode.

If the display is not viewable, press 

#

 twice.

The display will cycle through the range of
contrast settings. Press 

#

 again to lock in

the preferred contrast. 

ACCESSING THE MENUS. 

From the power-up

screen, pressing the Function keys indicated on the
LCD opens the associated menu. The menu opened
may list submenus that may be opened either directly
by pressing the associated Function keys, or by high-
lighting an item on the list and pressing the View/Mod-
ify function key. Menus and submenus will display a list
of parameters, with the top one highlighted. The func-
tion key assignments can vary, but generally offer the
following choices:

!

 allows the highlighted parameter to be

viewed or modified. After changing the param-
eter, the following choices are available: 

$

 -

SAVE or 

ENTER

 to save the change, 

%

  -

EXIT to abort the change and exit to the previ-
ous menu.

@

 - RESTORE DEFAULT restores factory

defaults for the parameters displayed (except
for GPIB address). The factory defaults may
be saved as power-up defaults by pressing

$

.

#

 - The function varies, depending on the

menu. In most cases 

#

 is used to abort a

change without applying the modified setting.
From the power-up screen 

#

 is used to

adjust contrast. In the Revisions/TEST sub-
menu of the General Setup Menu, 

#

 is used

to execute a test. 

$

 - SAVE FOR POWER-UP Saves the con-

figuration shown as a power-up setting so the
changes will not be lost when the unit is
turned off.

%

 - APPLY EXIT applies the current

(changed) setting without saving for power-up
and exits to the previous menu or to the
power-up screen, EXIT leaves the current
menu without saving or applying changes.

The menu structure is as follows (NOTE: 

BOLD

 = Fac-

tory Default):

Power-up Screen (Power up menu)

!

 - Save/Recall

Saved Setups: Recall one of 99 saved set-
ups.

Saved Setup Details: Mode (voltage/
current/External), main channel refer-
ence (internal/external/external refer-
ence level) and setting, Protection Type
(internal/external/LesserLimit) and set-
ting(s), output status (on/off)

@

 - Waveform 

Saved Waveforms: Choose one of 16
saved waveforms.

New Waveform Settings: Name (max.
10 characters), mode (voltage/current)
No. of cycles, +Protect, -Protect)

First segment: type (Square/ +ramp
/-ramp/triangle/sine/level),
Frequency, PtoP Amplitude, Offset 

Edit Waveform: Name, no. of cycles,
+protect, -protect, segment list, mode

Segment Details: Type ((Square/
+ramp/-ramp/triangle/sine/level/
slope/trigger), frequency or period,
amplitude, offset, start/stop angle

!

Summary of Contents for BOP 10-100ME

Page 1: ...siderations and operating instructions including an Installation Operation Summary which includes hyperlinked references to detailed procedures but which can be printed as a handy reference The BOP 1K...

Page 2: ...on After careful unpacking inspect for shipping damage before attempting to operate Perform the Load Connec tions on page 5 If any indication of damage is found file an immediate claim with the respon...

Page 3: ...e four feet first rack must provide support at the rear Optional slides may be used Leave the front and rear panels clear of obstruc tions to ensure adequate cooling Allow a minimum of 7 8 in above an...

Page 4: ...4 228 1692 REV 9 062119 KEPCO INC 131 38 SANFORD AVENUE FLUSHING NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 www kepcopower com email hq kepcopower com 1 FIGURE 1 BOP OUTPUT CHARACTERISTICS...

Page 5: ...odels only Connects BOP power supply to GPIB bus SNC 488 2 IEEE 488 Cable 4 meter longs For MG models only Connects BOP power supply to GPIB bus SNC 488 4 Interconnection Kits for parallel series conf...

Page 6: ...Port see Figure 3 provides for an external trigger input for use with SCPI TRG and TRIG commands Refer to Operator s manual for details GPIB CONNECTIONS MG SUFFIX Your computer must have a GPIB interf...

Page 7: ...AND INDICATORS RS 232 CONNECTIONS Connect the BOP 1KW to a modem using a Null Modem patch cable at the RS 232 port located on the rear panel See Figure 3 A Null Modem cable is not required for older...

Page 8: ...Y 11355 U S A TEL 718 461 7000 FAX 718 767 1102 www kepcopower com email hq kepcopower com FIGURE 3 BOP 1KW SERIES REAR PANEL VIEW LINKS INSTALLED FOR LOCAL SENSING FIGURE 4 LOAD CONNECTION A LOCAL SE...

Page 9: ...list and pressing the View Mod ify function key Menus and submenus will display a list of parameters with the top one highlighted The func tion key assignments can vary but generally offer the followi...

Page 10: ...on Shows Firmware versions for Display Serial GPIB LAN and analog Power up Settings Mode Voltage Cur rent External Main channel Reference Internal External ExtlRefLev main set ting Protection Type Int...

Page 11: ...ponding protection limit The main channel is determined by the MODE key in local mode which alternately selects either Voltage mode or Current mode or by SCPI com mand in digital remote mode The prote...

Page 12: ...rrent max min value and press to change it Software limits are absolute values do not use minus sign for nega tive limits Use number keys to change the set ting then to save 4 When complete press to s...

Page 13: ...g the power supply to load connections Resistive This mode as the name suggests is useful for resistive loads Table 6 indicates how the power supply responds to a command to go from Output ON to OFF V...

Page 14: ...stops energy flow during the OFF state Table 6 indicates how the power supply responds to a command to go from Output ON to OFF CONFIGURE LOAD TYPE To configure press from the power up screen then hi...

Page 15: ...power com email hq kepcopower com FIGURE 1 BOP 1KW OUTLINE DIMENSIONS SHEET 1 OF 2 20 000 508 00 21 439 544 54 22 800 579 11 21 564 547 73 22 000 558 79 23 863 606 12 18 235 463 16 18 985 482 21 1 470...

Page 16: ...UE FLUSHING NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 www kepcopower com email hq kepcopower com FIGURE 1 BOP 1KW OUTLINE DIMENSIONS SHEET 2 OF 2 SLIDES TRAVEL DISTANCE 23 000 584 2 22 000 558...

Reviews: