background image

2

228-1692 REV 9

 062119

KEPCO, INC. 



 131-38 SANFORD AVENUE 



  FLUSHING, NY. 11355 U.S.A.



  TEL (718) 461-7000



 FAX (718) 767-1102

www.kepcopower.com   



 email: [email protected]

I — DESCRIPTION.

The BOP 1KW-MG/ME Series hereafter referred to as
BOP, are true 4-quadrant programmable voltage and
current power supplies, meaning they are capable of
both sourcing and sinking power (see Figure 61).
These bipolar power supplies pass smoothly through
zero without switching to provide true ± voltage and ±
current. These BOP power supplies use switch mode
technology for low dissipation. A bi-directional, isolat-
ing, a-c input power factor correcting (PFC) circuit
recuperates energy sinked from an active load and
sends it back into the line to maintain low dissipation.

These BOP power supplies are controlled digitally from
a menu-driven front-panel keypad or one of the remote
digital interfaces (GPIB or RS 232 on MG models, LAN
or RS 232 on ME models) to set voltage and current
and the four protection limits (+voltage, –voltage, +cur-

rent and –current.) A front panel rotary adjuster allows
real-time adjustment of the output. A large LCD dis-
plays the mode of operation, the settings, and the
actual output voltage and current. Additionally, these
BOP models can be remotely controlled by an analog
±10V input for the main channel (voltage or current),
and a +1 to +10V input for the limit channels. 

BOP models are suitable for driving inductive loads
such as large magnets or motors, and for exercising
batteries. They are also suitable for characterizing
solar cell arrays, and powering many electrochemical
reactions. Models with L suffix have been optimized for
exceptionally low current ripple and noise and
improved stability (drift and temperature), making them
ideal for driving inductive loads, such as large magnets
or motors.

II — UNPACKING.

This instrument has been thoroughly inspected and
tested prior to packing and is ready for operation. After
careful unpacking, inspect for shipping damage before
attempting to operate. Perform the “Load Connec-
tions.” on page 5. If an
y indication of damage is found,

file an immediate claim with the responsible transport
service.

.

TABLE 1.  BOP 1KW-MG/ME MODEL PARAMETERS

Model 

(1)

d-c Output Range

Closed Loop Gain

Output Impedance

Voltage 

(2)

(V d-c)

Current

(A d-c)

Voltage 

Channel

G

V

 (V/V)

Current 

Channel

G

I

 (A/V)

Voltage Mode

(Series R - L)

Current Mode

(Parallel R - C)

R

d-c

(mOhms)

L

(

H)

R

d-c

(Ohms)

C

(

F)

1000 WATT MODELS

BOP 6-125MG/ME

0 to ±6

0 to ±125

0.6

12.5

0.05

1.5

24

1150

BOP 10-100MG/ME

0 to ±10

0 to ±100

1.0

10.0

0.1

2.0

50

1100

BOP 10-75MG/ME

0 to ±10

0 to ±75

1.0

7.5

0.13

2.0

67

976

BOP 20-50MG/ME

0 to ±20

0 to ±50

2.0

5.0

0.40

8.3

200

371

BOP 25-40MG/ME

0 to ±25

0 to ±40

2.5

4.0

0.63

15.8

313

165

BOP 36-28MG/ME

0 to ±36

0 to ±28

3.6

2.8

1.30

25

640

103

BOP 50-20MG/ME

0 to ±50

0 to ±20

5.0

2.0

2.50

50

1250

55

BOP 72-14MG/ME

0 to ±72

0 to ±14

7.2

1.4

5.14

104

2570

33

BOP 100-10MG/ME

0 to ±100

0 to ±10

10.0

1.0

10.0

163

5000

16

(1) Models with MG suffix include GPIB and RS 232 digital interfaces. Models with ME suffix include LAN and RS 232 digital interfaces.
(2)  When connecting active loads, the steady-state voltage of the active load must not exceed the maximum voltage rating of the BOP. 

Otherwise the overvoltage protection will shut down the power supply.

TABLE 2.  BOP-MEL/MGL 1000 WATT MODEL PARAMETERS

Model

(See Note 1.)

d-c Output Range

Closed Loop Gain

E

O Max

I

O Max

Voltage

Channel

Current

Channel

1000 WATT MODELS

BOP 10-100MEL/MGL

±10V d-c

±100A d-c

1.0

10.0

BOP 20-50MEL/MGL

±20V d-c

±50A d-c

2.0

5.0

BOP 36-28MEL/MGL

±36V d-c

±28A d-c

3.6

2.8

BOP 50-20MEL/MGL

±50V d-c

±20A d-c

5.0

2.0

NOTES: 1. MEL suffix models include LAN and RS 232 interfaces. MGL suffix models include GPIB and RS 232 interfaces.

2. When connecting active loads, the steady-state voltage of the active load must not exceed the maximum voltage rating of 

the BOP. Otherwise the overvoltage protection will shut down the power supply.

3. The output impedance of the MEL/MGL models is identical to the output impedance of corresponding ME/MG models.

Summary of Contents for BOP 10-100ME

Page 1: ...siderations and operating instructions including an Installation Operation Summary which includes hyperlinked references to detailed procedures but which can be printed as a handy reference The BOP 1K...

Page 2: ...on After careful unpacking inspect for shipping damage before attempting to operate Perform the Load Connec tions on page 5 If any indication of damage is found file an immediate claim with the respon...

Page 3: ...e four feet first rack must provide support at the rear Optional slides may be used Leave the front and rear panels clear of obstruc tions to ensure adequate cooling Allow a minimum of 7 8 in above an...

Page 4: ...4 228 1692 REV 9 062119 KEPCO INC 131 38 SANFORD AVENUE FLUSHING NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 www kepcopower com email hq kepcopower com 1 FIGURE 1 BOP OUTPUT CHARACTERISTICS...

Page 5: ...odels only Connects BOP power supply to GPIB bus SNC 488 2 IEEE 488 Cable 4 meter longs For MG models only Connects BOP power supply to GPIB bus SNC 488 4 Interconnection Kits for parallel series conf...

Page 6: ...Port see Figure 3 provides for an external trigger input for use with SCPI TRG and TRIG commands Refer to Operator s manual for details GPIB CONNECTIONS MG SUFFIX Your computer must have a GPIB interf...

Page 7: ...AND INDICATORS RS 232 CONNECTIONS Connect the BOP 1KW to a modem using a Null Modem patch cable at the RS 232 port located on the rear panel See Figure 3 A Null Modem cable is not required for older...

Page 8: ...Y 11355 U S A TEL 718 461 7000 FAX 718 767 1102 www kepcopower com email hq kepcopower com FIGURE 3 BOP 1KW SERIES REAR PANEL VIEW LINKS INSTALLED FOR LOCAL SENSING FIGURE 4 LOAD CONNECTION A LOCAL SE...

Page 9: ...list and pressing the View Mod ify function key Menus and submenus will display a list of parameters with the top one highlighted The func tion key assignments can vary but generally offer the followi...

Page 10: ...on Shows Firmware versions for Display Serial GPIB LAN and analog Power up Settings Mode Voltage Cur rent External Main channel Reference Internal External ExtlRefLev main set ting Protection Type Int...

Page 11: ...ponding protection limit The main channel is determined by the MODE key in local mode which alternately selects either Voltage mode or Current mode or by SCPI com mand in digital remote mode The prote...

Page 12: ...rrent max min value and press to change it Software limits are absolute values do not use minus sign for nega tive limits Use number keys to change the set ting then to save 4 When complete press to s...

Page 13: ...g the power supply to load connections Resistive This mode as the name suggests is useful for resistive loads Table 6 indicates how the power supply responds to a command to go from Output ON to OFF V...

Page 14: ...stops energy flow during the OFF state Table 6 indicates how the power supply responds to a command to go from Output ON to OFF CONFIGURE LOAD TYPE To configure press from the power up screen then hi...

Page 15: ...power com email hq kepcopower com FIGURE 1 BOP 1KW OUTLINE DIMENSIONS SHEET 1 OF 2 20 000 508 00 21 439 544 54 22 800 579 11 21 564 547 73 22 000 558 79 23 863 606 12 18 235 463 16 18 985 482 21 1 470...

Page 16: ...UE FLUSHING NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 www kepcopower com email hq kepcopower com FIGURE 1 BOP 1KW OUTLINE DIMENSIONS SHEET 2 OF 2 SLIDES TRAVEL DISTANCE 23 000 584 2 22 000 558...

Reviews: