background image

12

228-1692 REV 9

 062119

KEPCO, INC. 



 131-38 SANFORD AVENUE 



  FLUSHING, NY. 11355 U.S.A.



  TEL (718) 461-7000



 FAX (718) 767-1102

www.kepcopower.com   



 email: [email protected]

in while rotating the knob to modify the least
significant digit. 

Enter the desired value on the keypad using
the number keys. For example, to program the
BOP to 75.8V, press the following keys in
order 

75.8

 then press 

ENTER

. For fine

adjustment use 

Y

, and 

U

 to modify the least

significant digit. To correct the entry before
activation press the 

CLEAR

 key to set the

value to zero and start over. When the desired
value is displayed, press 

ENTER

. This causes

the new value to appear at the output and be
applied to the load if the output is enabled.

6. To program the corresponding Protect channel,

press 

Y

 or 

U

 as necessary to highlight the Pro-

tect channel. Then set the value using either of
the two methods described above. If the Protect
Entry setting is set to Independent, separate
entries for the positive and negative protect chan-
nel are possible. Otherwise the value entered is
applied to both positive and negative protect
channels.

NOTE: The BOP can be configured to show

the protection limits as either a single
value that applies to both protection
channels or show individual settings
for positive and negative protection
limits. Only voltage protection limits
are available when in current mode;
only current limits are available in volt-
age mode. See Operator’s Manual for
details.

SOFTWARE LIMITS.  

Software limits prevent pro-

gramming of the main channel or the Protect channel
beyond the software limit value. Refer to Operator’s
Manual for a full explanation of software limits.

Changing Main Channel Software limit. 

This procedure allows the user to determine the maxi-
mum value of voltage or current that can be pro-
grammed.

1. Press 

%

 from the power-up screen to enter the

General Setup menu, then highlight Max/Min Set-
tings. 

2. Press 

!

 to enter the Max/Min Settings submenu

(Figure 6). (If a Password is required, see Opera-
tor’s Manual for instructions.) 

3. Highlight the voltage or current max/min value

and press 

!

 to change it. Software limits are

absolute values (do not use minus sign for nega-

tive limits). Use number keys to change the set-
ting, then 

$

 to save. 

4. When complete, press 

$

 to save for power-up,

#

 to abort, or 

%

 to apply the changes (without

saving for power-up) and exit.

5. Upon return to the power-up screen, the main

channel (voltage or current) is compared against
the main channel limits in effect. If the main chan-
nel exceeds the limit, it is set to zero. 

6.  Highlight the ±CPROTECT or ±VPROTECT max/

min value and press 

!

 to change it. Software

limits are absolute values (do not use minus sign
for negative limits). Use number keys to change
the setting. Press 

$

 to save, or 

%

 to abort. 

7. When complete, press 

$

 to save for power-up,

or 

#

 to abort, or 

%

 to apply the changes (with-

out saving for power-up) and exit.

Upon return to the power-up screen, the new protection
limit (voltage or current) is compared against the pro-
tection limits in effect. If the new protection limit setting
is below the existing setting for the protection limit, the
protection channel (voltage or current) is set to zero.

DETERMINING HOW THE UNIT RESPONDS 

WHEN OUTPUT IS OFF (LOAD TYPE) 

 The

BOP supports three Load Type selections (see Table 6)
which determine how the power supply responds when
the output is off: ACTIVE, RESISTIVE and BATTERY.
The Load Type selection does not affect the settings of
the power supply for ON state; it only affects the mode
of operation, main internal reference level and the pro-
tection levels during the OFF state. 

WARNING

For inductive loads, and especially
superconducting magnet type
loads, the inherent offset of the
BOP in the OFF state may generate
significant current in the circuit. A
properly rated switch in parallel
with a resistor must be connected
between the power supply and the
load. The switch must be open and
the BOP front panel LCD must read
0V, 0A before removing or installing
connections between BOP and
load. 

Active.

 Active mode (default setting) is necessary for

the power supply to function properly and safely with
inductive loads and constant-current-type active elec-
tronic loads. Active mode can also be used with resis-
tive loads. Table 6 indicates how the power supply
responds to a command to go from Output ON to OFF.

Summary of Contents for BOP 10-100ME

Page 1: ...siderations and operating instructions including an Installation Operation Summary which includes hyperlinked references to detailed procedures but which can be printed as a handy reference The BOP 1K...

Page 2: ...on After careful unpacking inspect for shipping damage before attempting to operate Perform the Load Connec tions on page 5 If any indication of damage is found file an immediate claim with the respon...

Page 3: ...e four feet first rack must provide support at the rear Optional slides may be used Leave the front and rear panels clear of obstruc tions to ensure adequate cooling Allow a minimum of 7 8 in above an...

Page 4: ...4 228 1692 REV 9 062119 KEPCO INC 131 38 SANFORD AVENUE FLUSHING NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 www kepcopower com email hq kepcopower com 1 FIGURE 1 BOP OUTPUT CHARACTERISTICS...

Page 5: ...odels only Connects BOP power supply to GPIB bus SNC 488 2 IEEE 488 Cable 4 meter longs For MG models only Connects BOP power supply to GPIB bus SNC 488 4 Interconnection Kits for parallel series conf...

Page 6: ...Port see Figure 3 provides for an external trigger input for use with SCPI TRG and TRIG commands Refer to Operator s manual for details GPIB CONNECTIONS MG SUFFIX Your computer must have a GPIB interf...

Page 7: ...AND INDICATORS RS 232 CONNECTIONS Connect the BOP 1KW to a modem using a Null Modem patch cable at the RS 232 port located on the rear panel See Figure 3 A Null Modem cable is not required for older...

Page 8: ...Y 11355 U S A TEL 718 461 7000 FAX 718 767 1102 www kepcopower com email hq kepcopower com FIGURE 3 BOP 1KW SERIES REAR PANEL VIEW LINKS INSTALLED FOR LOCAL SENSING FIGURE 4 LOAD CONNECTION A LOCAL SE...

Page 9: ...list and pressing the View Mod ify function key Menus and submenus will display a list of parameters with the top one highlighted The func tion key assignments can vary but generally offer the followi...

Page 10: ...on Shows Firmware versions for Display Serial GPIB LAN and analog Power up Settings Mode Voltage Cur rent External Main channel Reference Internal External ExtlRefLev main set ting Protection Type Int...

Page 11: ...ponding protection limit The main channel is determined by the MODE key in local mode which alternately selects either Voltage mode or Current mode or by SCPI com mand in digital remote mode The prote...

Page 12: ...rrent max min value and press to change it Software limits are absolute values do not use minus sign for nega tive limits Use number keys to change the set ting then to save 4 When complete press to s...

Page 13: ...g the power supply to load connections Resistive This mode as the name suggests is useful for resistive loads Table 6 indicates how the power supply responds to a command to go from Output ON to OFF V...

Page 14: ...stops energy flow during the OFF state Table 6 indicates how the power supply responds to a command to go from Output ON to OFF CONFIGURE LOAD TYPE To configure press from the power up screen then hi...

Page 15: ...power com email hq kepcopower com FIGURE 1 BOP 1KW OUTLINE DIMENSIONS SHEET 1 OF 2 20 000 508 00 21 439 544 54 22 800 579 11 21 564 547 73 22 000 558 79 23 863 606 12 18 235 463 16 18 985 482 21 1 470...

Page 16: ...UE FLUSHING NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 www kepcopower com email hq kepcopower com FIGURE 1 BOP 1KW OUTLINE DIMENSIONS SHEET 2 OF 2 SLIDES TRAVEL DISTANCE 23 000 584 2 22 000 558...

Reviews: