B-10
BHK-MG 1/2 (OPR) 030916
B.37
OUTPut[:STATe]? QUERY
OUTP?
Syntax:
Short Form: OUTP[:STAT]?
Long Form: OUTPut[:STATe]?
Return Value: <int_value> (0 or 1)
Description:
Indicates whether power supply output is enabled or disabled.
Returns 0 if output disabled,
returns 1 if output enabled. Related Commands: OUTP. (See example, Figure B-1.)
B.38
[SOURce:]CURRent[:LEVel][:IMMediate][:AMPlitude] COMMAND
CURR
Syntax:
Short Form: [SOUR:]CURR[:LEV][:IMM][:AMP] <exp_value>
Long Form: [SOURce:]CURRent[:LEVel][:IMMediate][:AMPlitude] <exp_value>
<exp_value> = digits with decimal point and Exponent, e.g., 2.71E+1 for 27.1
Description:
Sets programmed current level at power supply output.
This command programs output current to
a specific value; actual output current will depend on load conditions. If the value exceeds the
CURR:LIM[:HIGH] value, error message -222,”Data out of range” is posted in output queue. Related
Commands: *RCL, *SAV, CURR:LIM[:HIGH]. (See example, Figure B-1.)
B.39
[SOURce:]CURRent[:LEVel][:IMMediate][:AMPlitude]? QUERY
CURR?
Syntax:
Short Form: [SOUR:]CURR[:LEV][:IMM][:AMP]? MIN, MAX
Long Form: [SOURce:]CURRent[:LEVel][:IMMediate][:AMPlitude]? MIN, MAX
Return Value:<exp_value> = digits with decimal point and Exponent, e.g., 2.71E+1 for 27.1
Description:
Returns either the programmed value, maximum value, or minimum value of current.
The
CURR? query returns the programmed value of current. Actual output current will depend on load con-
ditions. The CURR? MAX query returns the maximum current allowed for a particular model. CURR?
Returns programmed current value. CURR? MIN returns minimum current allowed for power supply
(always 0).
Related Commands: CURR. (See example, Figure B-1.)
B.40
[SOURCE:]CURRENT:LIMIT[:HIGH] COMMAND
CURR:LIM[:HIGH]
Syntax:
Short Form: [SOUR:]CURR:LIM[:HIGH] <exp_value>
Long Form: [SOURce:]CURRent:LIMit[:HIGH] <exp_value>
<exp_value> = digits with decimal point and Exponent, e.g., 2.71E+1 for 27.1
Description:
Sets limit for maximum power supply output current.
If the value exceeds the current protection
value (set by CURR:PROT, see PAR. B.44), error message -222,”Data out of range” is posted in the
output queue. NOTE: If the current limit is changed, any previously established trigger levels higher
than the new limit must be reprogrammed to be lower than the new limit; otherwise triggers will cause
the output to exceed the new limit. Once the limit is established, the unit will not accept trigger values
higher than the programmed limit. Related Commands: CURR. (See PAR. 3.3.5.1 and Figure 3-2 for
special programming considerations. See example, Figure B-4.)
B.41
[SOURce:]CURRent:LIMit[:HIGH]? QUERY
CURR:LIM[:HIGH]?
Syntax:
Short Form: [SOUR:]CURR:LIM[:HIGH]? Long Form: [SOURce:]CURRent:LIMit[:HIGH]?
Return Value:<exp_value> = digits with decimal point and Exponent, e.g., 2.71E+1 for 27.1
Description:
Returns value representing current limit set by CURR:LIM[:HIGH] command.
Related Com-
mands: CURR:LIM[:HIGH], CURR. (See example, Figure B-4.)
Summary of Contents for BHK-MG Series
Page 2: ......
Page 6: ......
Page 16: ......
Page 18: ...xii BHK MG030916 FIGURE 1 1 BHK MG 40W SERIES PROGRAMMABLE POWER SUPPLY...
Page 26: ...1 8 BHK 1 2 MG OPR 030916 FIGURE 1 3 RA 24 RACK ADAPTER WITH TWO 1 2 RACK BHK MG 40W UNITS...
Page 35: ...BHK 1 2 MG SERIES 030916 2 3 FIGURE 2 2 BHK MG SERIES REAR PANEL CONTROLS AND CONNECTIONS...
Page 100: ...3 54 BHK 1 2 MG 030916 FIGURE 3 20 SERIES AUTOMATIC CONFIGURATION...
Page 113: ...BHK 1 2 MG 030916 3 67 FIGURE 3 25 PARALLEL MASTER SLAVE CURRENT MODE CONFIGURATION...
Page 150: ......