6-5-1 SEALED SYSTEM DIAGNOSIS
Not Cooling Complaint
All components operating, No airflow problems, Not frosted up as a defrost problem
problem has been isolated to sealed system area
Frost
Pattern?
Equalization
Test
Partial
Very Fast
Inefficient
Compressor
Partial
Restriction
Complete
Restriction
Equalization
Test
Condenser
Temperature
None
Very Fast
Very Slow
Very Slow
Hotter than Normal
Air/Low Side
Leak
Loss of Change
Compressor Not
Pumping
Cap Tube
Sound
Room Temperature
Trace of Oil
Undercharge
Leak
Yes
No
Faint
Fast
None to Weak
(The equalization test is trying to restart a compressor after it has been operating.)