Kendrion Kuhnke Automation GmbH 

Construction and Functionality 

 

Vico MT

 (

E 863 GB

) 

28

 

01/10/2021 

 

4 Installation and Operation 

 

WARNING 

Consider the standards and regulations applicable in the country of use 

Improper installation may cause death and serious personal or property damage. 

Consider all standards and regulations applicable in the country of use and only have trained 
experts knowing all the formalities install the unit in machines or systems. 

 

 

Information 

Before installing, servicing or putting the unit into operation, please also read the safety 
information in the preface of this document. 

 

4.1  Mechanical Installation 

Vico MT is a modern electronic assembly. Handle – specifically mount, operate and service – with care. 

Whereas touch screens are generally very tough, you should still take account of a couple of basic facts 
when installing them. 

Check that the front of the housing is always flat and that the material is not warped, irrespective of which 
material is used. Do not expose the front panel to any mechanical pressure (bending stress). 

 Mounting Position 

By design, the unit may be installed vertically only. Not installing it according to instructions may prevent heat 
dissipation and therefore cause it to overheat, which may then provoke a loss in performance or cause the 
unit to switch off unexpectedly. 

Take particular care not to place the unit on a table top or the floor to operate it. 

 

 

CAUTION 

Risk of overheating and fire! 

Even if operated at admissible ambient temperature, the unit may be destroyed if the way of 
installation stops the convection cooling from working. 

  Please take heed of the notes on the mounting position. 

 

Leave some free space above, beneath, at the sides and back of the unit to allow enough air to circulate. Be 
sure to leave at least 50 mm of free space on all sides. This specification applies to all variants. 

 

 

Summary of Contents for Vico MT 1027

Page 1: ...User Guide Vico MT 727 Vico MT 1027 Vico MT 1527 Multi touch Panel with CODESYS HMI Web Terminal E 863 GB 01 10 2021...

Page 2: ...lity 10 2 Product Description 12 2 1 General Description 12 Software Releases 12 Hardware Versions 13 2 2 Application 14 Intended Use 14 Foreseeable Misuse 14 2 3 Technical Data 15 Vico MT 15 Dimensio...

Page 3: ...urity 34 4 5 Configuration 35 4 6 Diagnosis 36 4 7 Table of Faults 36 4 8 Maintenance Servicing 37 General 37 Servicing 37 Preventive Maintenance 37 4 9 Life Expectancy 38 Repairs Customer Service 38...

Page 4: ...43 6 2 Drawings 44 Dimensions of Vico MT 727 44 Installation Opening of Vico MT 727 45 Font View of Vico MT 727 45 Dimensions of Vico MT 1027 46 Installation Opening of Vico MT 1027 47 Front View of V...

Page 5: ...2 About this Manual This technical information is primarily directed to system designers project engineers and device developers It does not contain any availability information We reserve the rights...

Page 6: ...Cortex are registered trademarks of ARM Limited Modbus is a registered trademark of the Modbus IDA Organisation The companies mentioned herein own the property rights in their company product and trad...

Page 7: ...f automation technology is compulsory Intended Use Kendrion s products are designed developed and manufactured for standard industrial use They must not be used for any other purposes than the ones sp...

Page 8: ...makes you aware of a potentially hazardous situation which MAY cause a serious or fatal accident or damage to this or other devices if not observed CAUTION A CAUTION alert makes you aware of a potenti...

Page 9: ...lified applications have to be complied with Please pay particular attention to the notices of warning which at relevant places will make you aware of possible sources of dangerous mistakes or faults...

Page 10: ...and immunity to interference of programmable logic controllers are internationally governed by standard IEC 61131 2 which in Europe has been the basis for European Standard EN 61131 2 Information Refe...

Page 11: ...e suitable casings to avoid possible negative influences due to humidity corrosive gas liquid or conducting dust Impact and Vibration Consider possible influences caused by motors compressors transfer...

Page 12: ...browser look and behaviour keyboard and language settings a boot screen or screen saving showing your logo and many other properties Software Releases Various software options or combined software op...

Page 13: ...Product Description Vico MT E 863 GB 13 01 10 2021 Hardware Versions The unit sells with screens of various sizes but the same control unit at the back Front view of Vico MT 727 Front view of Vico MT...

Page 14: ...conditions and the unit s mounting position Foreseeable Misuse Do not use in explosive atmospheres DANGER Do not use in explosive atmospheres Using the unit in explosive atmospheres may cause death or...

Page 15: ...rd slot up to SDXC Networks 1x Ethernet 1 Gbit RJ45 1x Ethernet 10 100 1000 Mbit RJ45 Ports 2x USB 2 0 host 1x RS 232 no electrical insulation Power supply 24 VDC 20 20 Power consumption 550 mA 580 mA...

Page 16: ...Kendrion Kuhnke Automation GmbH Product Description Vico MT E 863 GB 16 01 10 2021 Dimensions Refer to section 8 for exact dimensions 8 2 Dimensions...

Page 17: ...creen allows users to run all display and operating functions in a single unit It is designed for on site use immediately at the machine Mechanical system and cabinet engineers benefit from the unit s...

Page 18: ...2 RS232 Kendrion Kuhnke Automation GmbH L tjenburger Strasse 101 23714 Malente Germany Vico MT 727 24 V 550 mA max Typ CODESYS HMI OrderNo 677 810 01 Ident No 199888 Prot IP 65 IP20 Def IPNet1 192 168...

Page 19: ...are release date It is a means of traceability Make up of serial number YY MM DD NNNNN Example The unit shown above was manufactured on 03rd August 2021 and has the serial number 00270 21 08 03 00270...

Page 20: ...re that the ambient conditions are as specified at all times during transport and storage Refer to manual section 9 6 3 Admissible Ambient Conditions for admissible ambient and transport condition det...

Page 21: ...plug in type X3 MicroSD X5 NET1 X9 USB2 USB1 X1 Power FE 0V 24V X6 NET2 X12 RS232 Kendrion Kuhnke Automation GmbH L tjenburger Strasse 101 23714 Malente Germany Vico MT 727 24 V 550 mA max Typ CODESYS...

Page 22: ...Supply Pin Signal Function 1 OE operative earth 2 0 V external 0 V power supply 3 24V external power supply 24 VDC 18 V 32 V Connection data X9 Mating Connector Type screwed connection with spring bu...

Page 23: ...d for use in industrial environments but just as a service interface for loading software updates or data up into or down from the control unit USB sticks USB stick users should consider the following...

Page 24: ...TX 3 D2 RX 4 D3 5 D3 6 D2 RX 7 D4 8 D4 LED LNK green orange data link LED RCV orange activity Ethernet NET2 X6 The on board 10 100 Mbit base T Ethernet adapter attaches the unit to a network through...

Page 25: ...at an RS232 signal level It is not electrically isolated Pin wiring Cable shorter than 3 m shielded X7 RS 232 interface Connector Pin Function 1 2 RxD RS232 Receive Data 3 TxD RS232 Transmit Data 4 5...

Page 26: ...ustrial environments you should preferably use industry grade SD cards instead of commercial ones Features of industry grade SD cards SLC or iMLC memory Secure write and clear cycles Longer period of...

Page 27: ...further details Screen The IPS displays installed reliably reproduce colours and provide a wide aspect angle Backlight Use the system setup utility or a Linux command to set the backlight brightness...

Page 28: ...facts when installing them Check that the front of the housing is always flat and that the material is not warped irrespective of which material is used Do not expose the front panel to any mechanical...

Page 29: ...4 5 mm Please note the drawing 7 display panels Approaching the switching cabinet from the front slide the unit into the opening and gently push it all the way in until it contacts the cabinet front A...

Page 30: ...panel control unit is mounted correctly at all times In order to achieve the specified ingress protection the material must not warp under the load of the mounting bolts or operation 10 1 or larger d...

Page 31: ...ductor shielding check that all data link cables attached to the unit have shielded wires and attach to the unit s earthing terminals WARNING Malfunction due to improper earthing of the unit The unit...

Page 32: ...Voltage output power 24 VDC min 30 W Power supply fusing The cord must have external protection against short circuit and overload triggering at max 10 A min 60 V NOTE Damage to connectors or cables b...

Page 33: ...finger or a suitable stylus NOTE Damage to the touch screen by pointed or hard objects Destruction of front Do not use pointed or hard objects to operate the touch screen Avoid sudden or impact like t...

Page 34: ...rvices drivers protocols RPC HTTP S Authentication encoding compulsory registration encrypted password Physical access closed rooms cabinets Third party systems or personnel Take every effort to avoid...

Page 35: ...y to configure the units of this series You can choose to start the configuration utility either directly by picking the appropriate option as the unit starts up or by running an Internet browser on a...

Page 36: ...supplied Date and time are not stored permanently The time is lost after a power failure Periodically synchronise using the Network Time Protocol NTP Touch screen No function Overreacts The unit is no...

Page 37: ...turn it off before you clean its front panel CAUTION Unintentional start of functions Movements of machine parts In order to avoid unintentionally starting a function by touching the screen or pressi...

Page 38: ...authorised attempts are made to repair the unit product or any other intervention is performed Taking out of Service Disposal Disposal requires the device to be disassembled and entirely taken apart A...

Page 39: ...n external device and configuring the unit via its Ethernet connection The menus are arranged well to help you quickly find a particular setting such as the network settings URL display FTP IP tables...

Page 40: ...ating systems and some network devices Disks The Disk settings define how the connected drives such as thumb drives will behave Fonts The Fonts category lists all fonts currently installed on your sys...

Page 41: ...to create edit the shell script Backup Restore Use this menu item to back up or restore the settings of the system and the application or the entire system This function live system provides you with...

Page 42: ...Use this function to install further files fonts or Linux packages or to change any of the system settings To do so create an init directory on a thumb drive and save your scripts there All scripts i...

Page 43: ...tails regarding the software resources concerned CODESYS Control runtime system Equipment manufacturers installing the CODESYS runtime system on their devices are sent a licence file when they purchas...

Page 44: ...Kendrion Kuhnke Automation GmbH Construction and Functionality Vico MT E 863 GB 44 01 10 2021 6 2 Drawings Dimensions of Vico MT 727...

Page 45: ...Kendrion Kuhnke Automation GmbH Construction and Functionality Vico MT E 863 GB 45 01 10 2021 Installation Opening of Vico MT 727 Font View of Vico MT 727...

Page 46: ...Kendrion Kuhnke Automation GmbH Construction and Functionality Vico MT E 863 GB 46 01 10 2021 Dimensions of Vico MT 1027...

Page 47: ...Kendrion Kuhnke Automation GmbH Construction and Functionality Vico MT E 863 GB 47 01 10 2021 Installation Opening of Vico MT 1027 Front View of Vico MT 1027...

Page 48: ...Kendrion Kuhnke Automation GmbH Construction and Functionality Vico MT E 863 GB 48 01 10 2021 Vico MT1527...

Page 49: ...Kendrion Kuhnke Automation GmbH Construction and Functionality Vico MT E 863 GB 49 01 10 2021 Installation Opening of Vico MT1527 Front View of Vico MT1527...

Page 50: ...strial environments Admissible Ambient Conditions Storage and transport Temperature 20 70 C Relative humidity 10 to 95 at 25 C no condensation Operation Place of use industrial environment indoor use...

Page 51: ...o the competent authorities pursuant to the above EU Directive Please contact the Project Management as necessary 6 5 Approvals The series of units has been granted the following approvals RoHS Confor...

Page 52: ...ARM Cortex A53 i MX8Mmini quad core CPU 4x 1 6 GHz Housing aluminium at front IP65 stainless steel at back IP20 Power supply 24 VDC 20 Vico MT 727 WEB 677 810 01 Web terminal with multi touch screen...

Page 53: ...Kendrion Kuhnke Automation GmbH Construction and Functionality Vico MT E 863 GB 53 01 10 2021 Accessories...

Page 54: ...Kendrion Kuhnke Automation GmbH Industrial Control Systems L tjenburger Str 101 D 23714 Malente Tel 49 4523 402 0 Fax 49 4523 402 201 sales ics kendrion com www kendrion com...

Reviews: