- 27 -
3.2.1 Adding drinking water temperature sensors
In the recording mode select the navigation point "Add components" and enter the number of your existing
temperature sensors for the monitoring function. Confirm your entry with the "OK" button.
Important:
The same identical sensor cannot be used simultaneously for flushing and for recording.
3.2.2 Configuring drinking water temperature sensors
As you can see in the symbolic representation in the sample project, there is only one hygienic flushing.
In this case the hygienic flushing has Channel 1 (101) and is triggered with time control.
There is no other way to trigger during hygienic flushing.
You also have a facility for editing the comments and the names as you desire. Subsequently
confirm the changes with "OK". To add more hygienic flushings, proceed likewise.
Now please set the properties of the sensor selected for the monitoring:
When will a thermal disinfection start running?
Starting at what point is the set point exceeded and at what point is it undercut; these overruns
and undercuts are then written into the temperature log.
Please enter the type of sensor under sensor type.