Function test of solenoid valve in tank cleaning unit
2.5
To prevent the solenoid valve from getting stuck, it
must undergo a function test during every mainte-
nance.
Press the
Main Menu
button on the initial display.
Scroll down with the arrow key to
Drain
tank
and
confirm
with OK.
1
2
The display shows the confirmation
solenoid valve open
.
- Leave the valve open for 10 seconds, then
exit the
menu
with the arrow key (bottom left).
The solenoid valve closes automatically when you
exit the menu.
Use the
arrow key
to return to the initial display.
3
4
Main menu
Operating modes
Cleaning
Process
Main menu
1. System settings
2. Pump
3. Messages
4. Empty tank
5. Inlet control
Empty tank
Inlets closed
Solenoid valve
On/Off
Pump controller
On
2.
1.