18 /16 – K410036900017-00 / 10.2022 – ©
www.kemper-group.com
2.3
Checking the overflow
EN
According to EN 806-5, the overflow must be visually inspected,
and its permeability checked.
Function test of overflow monitoring device
2.4
The overflow monitor is a safety device that stops the water
supply to the break tank station as soon as water is forced back
out of the drainage system.
X
X
X
1
2
Remove the yellow cap from the tank.
Inspect the overflow from above (photo).
Replace the cap.
3
Use a screwdriver to lift the float
upwards.
After 2 seconds, the controller reports an error and a
buzzer sounds.
1
2
Press the button to call up the error message.
The error message can
be
acknowledged with OK.
After the error message, the plant is switched off.
In the menu item Operating modes, the break tank
station must be switched on again.
3
Overflow at free drain!
Main menu
Operating modes
Cleaning
Process
Summary of Contents for FK-5
Page 12: ...12 16 K410036900017 00 10 2022 www kemper group com 4 Wartungsprotokoll DE...
Page 13: ...www kemper group com K410036900017 00 10 2022 13 16 4 Wartungsprotokoll...
Page 14: ...14 16 K410036900017 00 10 2022 www kemper group com 4 Wartungsprotokoll DE...
Page 25: ...www kemper group com K410036900017 00 10 2022 25 16 4 Maintenance protocol...
Page 26: ...26 16 K410036900017 00 10 2022 www kemper group com 4 Maintenance protocol EN...
Page 27: ...www kemper group com K410036900017 00 10 2022 27 16 Maintenance protocol 4...