Maintenance work
EN
Inspections can be carried out by the operator.
Maintenance must be carried out by authorised qualified personnel.
I = inspection
M = maintenance
FK-5 maintenance schedule (recommendations)
Interval
Maintenance work
Comments
I / M
Every 2 months
Check all connections and screw connections
If necessary, retighten and/or replace gaskets
I
General visual inspection of all components for dam-
age
In case of damage, run a functional check and replace
if necessary
I
Every 6 months
Check free drain
Flow limiter OK, inlet closing tightly – see
EN 806 Part 5
I
Check function of maintenance cut-offs
Valves open and close
I
Additionally, every 12 months Function check of the pump
Switch on pump, and check pressure and flow
M
Check the pump operating cycle meter
Replace pump relay after 100,000 switching cycles
M
Check waste water connection
Drainage capacity OK, adequate water level in trap
M
Manually trigger overflow monitoring (optional)
Float must move freely
M
Check the casing
Replace if damaged, and check for correct fit
M
Check anti-pollution check valve
Max. system pressure must remain constant for 5 min
M
Clean the dirt trap (fig. 60200)
Replace cover gasket if necessary
M
Check tank emptying or solenoid valve of the tank
cleaning unit
Drain the container for approx. 10 seconds
M
Check the quarter turn stop valve
Valves close tightly and move smoothly
M
Check the quarter turn stop valve actuators
Retighten motors if necessary, and check positioning
M
Check electrical wiring
M
Check time and date
M
Update software
See operating instructions section 6.0
M
Download and read the log files
See operating instructions section 5.0
M
Inspect expansion tank
Correct pressure if necessary
M
Replace components
Interval
Components
Comments
I / M
Additionally, every 24 months Change quarter turn stop valve
See operating instructions section 6.4
M
Every 100,000 switching cycles Change pump relay
See operating instructions section 9.0
M
Summary of Contents for FK-5
Page 12: ...12 16 K410036900017 00 10 2022 www kemper group com 4 Wartungsprotokoll DE...
Page 13: ...www kemper group com K410036900017 00 10 2022 13 16 4 Wartungsprotokoll...
Page 14: ...14 16 K410036900017 00 10 2022 www kemper group com 4 Wartungsprotokoll DE...
Page 25: ...www kemper group com K410036900017 00 10 2022 25 16 4 Maintenance protocol...
Page 26: ...26 16 K410036900017 00 10 2022 www kemper group com 4 Maintenance protocol EN...
Page 27: ...www kemper group com K410036900017 00 10 2022 27 16 Maintenance protocol 4...