K°Bloc – Fully welded plate heat exchangers - English Version 2.2 - 01.2016
86
7.4.2.2
TIGHTENING THE PANEL – TO THE SPECIFIED TORQUE ON PANELS
WITHOUT CORNER BOLT HOLE
Requirement:
You must know the permitted tightening torques. You can find these in
the technical documentation or on the name plate of the K°Bloc.
Carry out the following steps:
1.
Tighten all nuts of panel "I" to 20 % of the maximum torque crosswise
from 1 to 22 according to the exemplary figure below.
Figure 7.4.2.2.a