background image

 Kelvinator Gas Continuous Flow hot water system 

 clearances  9

Clearances for outdoor heater locations – 

AS5601 

f

c

k

k

j

j

j

h

h

h

T

T
g

e

e

a

d

b

c

g

T

d

see note 2

T –   Flue terminal 

I –   Mechanical air inlet

M –   Gas meter 

P –   Electricity meter  

 

or fuse box

Shading indicates prohibited 

areas for flue terminals

see note 3 

P

n

openable 

window

Reference

Item

Minimum clearances (mm)

a

Below eaves, balconies and other projections:
• appliances up to 50MJ/h input

200

• appliances over 50MJ/h input

300

b

From the ground above a balcony surface*

300

c

From a return wall or external corner*

300

d

From a gas meter (M) (see 4.7.11 for vent terminal location  
of regulator)

1000

e

From an electricity meter or fuse box (P) 

500

f

From a drain or soil pipe 

75

g

Horizontally from any building structure* or obstruction facing 
a terminal 

500

h

From any other flue terminal, cowl or combustion air intake 

300

j

Horizontally from an openable window, door, non-mechanical 
air inlet or any other opening into a building with the exception 
of sub-floor ventilation
• Appliances up to 150 MJ/h input

300

• Appliances over 150 MJ/h input up to 200 MJ/h input

500

• Appliances over 200 MJ/h input

1500

• All fan-assisted flue appliances in the direction of discharge

1500

k

From a mechanical air inlet, including a spa blower

1000

n

Vertically below an openable window, non-mechanical air  
outlet or any other opening into a building with the exception 
of sub-floor ventilation
• Space heaters up to 50 MJ/h input

150

• Other appliances up to 150 MJ/h input

500

• Appliances over 50 MJ/h input up to 150 MJ/h input

1500

• Appliances over 150 MJ/h input

1500

*unless appliance is certified for closer installation.

NOTES:
1.  All distances are measured to the nearest part of the 

terminal.

2.  Prohibited area below electricity meter or fuse box 

extends to ground level.

3.  See clause 15.3.6.6 for restrictions on a flue terminal 

under a covered area.

4.  See Appendix J, figures J2(a) and J3(a) for clearances 

required from a flue terminal to an LP gas cylinder. A flue 
terminal is considered to be a source of ignition.

5.  For appliances not addressed above, acceptance should 

be obtained from the technical regulator.

Exemption from prescribed statuatory requirements 
referred to above has been granted to allow multiple series 
of the water heaters to be positioned side by side.

This diagram and reference table has been taken from the AS/NZS 5601 standard regarding gas installations. Any references on this page to 

clauses or appendix figures are referring directly to this standard.

Summary of Contents for KGC20BNA

Page 1: ...Gas Continuous Flow Hot Water System Installation Manual...

Page 2: ...s gas continuous hot water system please contact your local authorities and ask for the correct method of disposal caution The hot water system is not intended for use by young children or infirm pers...

Page 3: ...n concerning use by a person responsible for their safety Children should be supervised to ensure that they do not play with the gas continuous flow hot water system This symbol indicates never to do...

Page 4: ...y or loss of life 1 The gas continuous flow hot water system does not have a pilot It is equipped with an internal ignition device that automatically lights the burner Do not try and light the burner...

Page 5: ...GC26KNA KGC26SNA KGC26BLA KGC26KLA KGC26SLA Capacity L min 20L min 26L min Gas Input MJ h 160 195 Supply Inlet Pressure kPa Nat Gas 1 13 min 1 13 min 2 75 max 2 75 max Supply Inlet Pressure kPa LPG 2...

Page 6: ...A KGC20KLA KGC20SNA KGC20SLA 124mm 490mm 520mm 31mm power 47mm gas 133mm 94mm 60mm 198mm 350mm top fixing positions top fixing positions 330mm hot 98mm 70mm 108mm 30mm cold gas 335mm 19mm 37mm 49mm co...

Page 7: ...Exterior view KGC26BNA KGC26BLA KGC26KNA KGC26KLA KGC26SNA KGC26SLA power cold 84mm 34mm gas 124mm 133mm hot 41mm hot 49mm cold 490mm 520mm 25mm power 44 5mm gas 350mm 37mm 19mm 198mm 330mm 94mm 60mm...

Page 8: ...and 70 C models The water heater requires a fireproof back plate if installed on timber wall Selecting an installation location Carefully read this section before selecting the installation location a...

Page 9: ...ll fan assisted flue appliances in the direction of discharge 1500 k From a mechanical air inlet including a spa blower 1000 n Vertically below an openable window non mechanical air outlet or any othe...

Page 10: ...onnect any water lines to the gas inlet It may be critically damaged power cord gas inlet supply gas valve Sizing and connection Check the gas type label to make sure that the water heater was built f...

Page 11: ...systems A manual shut off valve must be installed on the cold water inlet to the water heater between the main water supply line and the water heater Only a gate valve or a ball valve is to be used on...

Page 12: ...rules 5 The insulation of the fixed wiring must be protected by insulating sleeving having an appropriate temperature rating 6 If the supply cord is to be replaced this must be done by a service techn...

Page 13: ...n or water heater the remote controller will display a numerical error code Main remote controller model KGCMRCA KGCMRCA must be installed inside as it is NOT water resistant Allows the output tempera...

Page 14: ...to attach the remote control to gyprock you should use the anchor plug use the fork terminals 25mm remote control wiring connector base 83 5mm 45mm warning The remote controller must be installed insi...

Page 15: ...onnect remote control wires to remote terminals directly There is no polarity in the terminations plastic cover KGCMRCA typical cable layout remote control terminal remote control cable Remove the pla...

Page 16: ...inlet to the water heater 7 Check the gas pipe work for leaks and stop the leaks as necessary caution If there is a gas leak that cannot be stopped do not try to start the water heater Do not touch a...

Page 17: ...n to be handed to the customer or left in a suitable location on the premises If the customer is available they are to be instructed on the safe and correct operating of the water heater and any auxil...

Page 18: ...o keep the water heater running Is the gas supply valve fully open Is the filter on the cold water inlet clean Are the fixtures clean of debris and obstructions Fluctuation in hot water temperature Is...

Page 19: ...he bottom left hand side of the cabinet and the error codes can be read from the LED on the PCB Error Codes on the PCB The LED on the PCB Symptom LED light blinks once Incorrect dipswitch setting gas...

Page 20: ...20 notes Kelvinator Gas Continuous Flow hot water system Notes...

Page 21: ...Kelvinator Gas Continuous Flow hot water system notes 21 Notes...

Page 22: ...22 notes Kelvinator Gas Continuous Flow hot water system Notes...

Page 23: ...is transported at the owner s cost and risk while in transit to and from Electrolux or its ASC 6 Proof of purchase is required before you can make a claim under this warranty 7 You may not make a clai...

Page 24: ...er information about Kelvinator appliances please visit your retailer phone or email our Customer Care team or visit our website telephone 1300 363 640 fax 1800 350 067 email customercare electrolux c...

Reviews: