Measuring inlet gas pressure and testing gas leakage

The inlet gas pressure to the water heater should be checked  
and leak tested before operating for the first time. 

This is 

only to be done by a licensed professional. 

1.   Shut off the manual gas valve on the supply gas line. 
2.   Open a faucet. The water heater should turn on and the 

gas in the gas pipe line should purge. Leave the faucet on 
to keep the water heater running until it shuts down due 
to lack of gas supply. Then shut the faucet off. 

3.   Remove the screw for the pressure port located on the 

gas inlet of the water heater shown in the diagram below. 

4.   Connect the manometer to the pressure port. 
5.   Re-open the manual gas valve. Check to see that there 

are no gas leaks. 

6.   Open some of the fixtures that use the highest flow rate 

to turn on the water heater. 

7.   Check the inlet gas pressure. When the water heater is on 

a maximum burn, the inlet gas pressure within must be 
within the appropriate range. (Please refer to page 5) 

This water heater and its individual shut-off valve must be 
isolated from the gas supply piping system by unplugging 
the water heater and turning off the main gas valve during 
any pressure testing of the gas supply piping system at test 
pressures above 3kPa.

10  gas connection 

 Kelvinator Gas Continuous Flow hot water system

Gas connection

caution

1.  Turn off the electrical supply to the water heater and 

manual gas valve located on the outside of the water 
heater before beginning gas connection. 

2.   Confirm the position of the gas inlet. Do not connect 

any water lines to the gas inlet. It may be critically 
damaged.

      

      

      

      

 

 

 

 

 

power cord

gas inlet supply

gas valve

Sizing and connection

Check the gas type label to make sure that the water heater 
was built for the type of gas you will be using, and that the 
gas inlet pressure is within the appropriate range. (Please 
refer to page 5) 
1.   Gas pressure below this specified range for the water 

heater and/or insufficient gas volume will adversely affect 
performance. 

2.   Inlet gas pressure must not exceed the above maximum 

values; gas pressure above the specified  range will cause 
dangerous operating conditions and damage to the 
water heater. 

3.   Until testing of the main gas line supply pressure is 

completed, ensure the gas line to the water heater is 
disconnected to avoid any damage to the water heater

warning

Conversion of this water heater from natural gas to 
propane or propane to natural gas cannot be done in the 
field. Contact your local retailer or distributor to get the 
correct water heater for your gas type. 

•  Size the gas piping according to AS5601 installation code 

for the correct pipe sizing for the water heater. 

•  Always use approved connectors to connect the water 

heater to the gas line. The service technician should 
purge the gas line of any debris before connecting to the 
water heater. 

•  Install a manual gas shut-off valve between the water 

heater and the gas supply line. 

•  The regulator is preset at the factory. It is computer 

controlled and is not to be adjusted by any person other 
than a qualified Service Provider. 

•  When the gas connections are completed, it is necessary 

to perform a gas leak test either by applying soapy water 
to all gas fittings and observing for bubbles or by using a 
gas leak detection device.

Summary of Contents for KGC20BNA

Page 1: ...Gas Continuous Flow Hot Water System Installation Manual...

Page 2: ...s gas continuous hot water system please contact your local authorities and ask for the correct method of disposal caution The hot water system is not intended for use by young children or infirm pers...

Page 3: ...n concerning use by a person responsible for their safety Children should be supervised to ensure that they do not play with the gas continuous flow hot water system This symbol indicates never to do...

Page 4: ...y or loss of life 1 The gas continuous flow hot water system does not have a pilot It is equipped with an internal ignition device that automatically lights the burner Do not try and light the burner...

Page 5: ...GC26KNA KGC26SNA KGC26BLA KGC26KLA KGC26SLA Capacity L min 20L min 26L min Gas Input MJ h 160 195 Supply Inlet Pressure kPa Nat Gas 1 13 min 1 13 min 2 75 max 2 75 max Supply Inlet Pressure kPa LPG 2...

Page 6: ...A KGC20KLA KGC20SNA KGC20SLA 124mm 490mm 520mm 31mm power 47mm gas 133mm 94mm 60mm 198mm 350mm top fixing positions top fixing positions 330mm hot 98mm 70mm 108mm 30mm cold gas 335mm 19mm 37mm 49mm co...

Page 7: ...Exterior view KGC26BNA KGC26BLA KGC26KNA KGC26KLA KGC26SNA KGC26SLA power cold 84mm 34mm gas 124mm 133mm hot 41mm hot 49mm cold 490mm 520mm 25mm power 44 5mm gas 350mm 37mm 19mm 198mm 330mm 94mm 60mm...

Page 8: ...and 70 C models The water heater requires a fireproof back plate if installed on timber wall Selecting an installation location Carefully read this section before selecting the installation location a...

Page 9: ...ll fan assisted flue appliances in the direction of discharge 1500 k From a mechanical air inlet including a spa blower 1000 n Vertically below an openable window non mechanical air outlet or any othe...

Page 10: ...onnect any water lines to the gas inlet It may be critically damaged power cord gas inlet supply gas valve Sizing and connection Check the gas type label to make sure that the water heater was built f...

Page 11: ...systems A manual shut off valve must be installed on the cold water inlet to the water heater between the main water supply line and the water heater Only a gate valve or a ball valve is to be used on...

Page 12: ...rules 5 The insulation of the fixed wiring must be protected by insulating sleeving having an appropriate temperature rating 6 If the supply cord is to be replaced this must be done by a service techn...

Page 13: ...n or water heater the remote controller will display a numerical error code Main remote controller model KGCMRCA KGCMRCA must be installed inside as it is NOT water resistant Allows the output tempera...

Page 14: ...to attach the remote control to gyprock you should use the anchor plug use the fork terminals 25mm remote control wiring connector base 83 5mm 45mm warning The remote controller must be installed insi...

Page 15: ...onnect remote control wires to remote terminals directly There is no polarity in the terminations plastic cover KGCMRCA typical cable layout remote control terminal remote control cable Remove the pla...

Page 16: ...inlet to the water heater 7 Check the gas pipe work for leaks and stop the leaks as necessary caution If there is a gas leak that cannot be stopped do not try to start the water heater Do not touch a...

Page 17: ...n to be handed to the customer or left in a suitable location on the premises If the customer is available they are to be instructed on the safe and correct operating of the water heater and any auxil...

Page 18: ...o keep the water heater running Is the gas supply valve fully open Is the filter on the cold water inlet clean Are the fixtures clean of debris and obstructions Fluctuation in hot water temperature Is...

Page 19: ...he bottom left hand side of the cabinet and the error codes can be read from the LED on the PCB Error Codes on the PCB The LED on the PCB Symptom LED light blinks once Incorrect dipswitch setting gas...

Page 20: ...20 notes Kelvinator Gas Continuous Flow hot water system Notes...

Page 21: ...Kelvinator Gas Continuous Flow hot water system notes 21 Notes...

Page 22: ...22 notes Kelvinator Gas Continuous Flow hot water system Notes...

Page 23: ...is transported at the owner s cost and risk while in transit to and from Electrolux or its ASC 6 Proof of purchase is required before you can make a claim under this warranty 7 You may not make a clai...

Page 24: ...er information about Kelvinator appliances please visit your retailer phone or email our Customer Care team or visit our website telephone 1300 363 640 fax 1800 350 067 email customercare electrolux c...

Reviews: