A means for disconnection of the F29 must be incorporated in the fixed
wiring in accordance with the wiring rules.
If a blackout or brownout occurs the F29 will not retain any memory of
where in its run or stop cycle it may have been, it will simply shut down
the pump. When power resumes, the F29 will reboot, restart the pump
and run any timer settings from the beginning. A manual reboot can be
done at any time by pressing and releasing the F29’s reset button.
The F29 has 3 X M20 cable glands. As supplied, the cable glands are
blanked off with rubber plugs. To use the glands first remove one of the
rubber plugs and assemble the (supplied) cable gland bush and backing
washer into the cable port. The cable glands can accept cable from 7 to
9mm diameter. See sketch for assembling the cable gland components.
The F29 is supplied with a set of steel crimp rings. The crimp rings are to
provide strain relief for the controller’s cables. To use the crimps, place
one on the cable approximately 3 to 4mm below the end of the cables outer
sheathing. Crimp the two ears of the ring flat using bull nosed pliers. Pull
the cable back through the cable gland until the crimp ring’s ears are fully
located into the slots in the cable gland housing. Always leave unused
cable glands sealed off using the (supplied) rubber plugs.
The HD terminal must be left unused or only ever linked to Relay 1
Normally Open. It must never be used for any other purpose and it
must never be connected to any external device. Under no
circumstances connect the HD terminal to the terminals of Relay 2. The
HD terminal must be regarded as live at all times and at full mains
potential.
CABLES
IMPORTANT
BROWNOUT OR BLACKOUT
WARNING