RELAYS
MAXIMUM PUMP MOTOR LOAD FOR RELAY 1
POWER REQUIRED TO DRIVE THE 12VDC F29-12
POWER REQUIRED TO DRIVE THE STANDARD F29
10A at 240VAC 2.4kW
24VDC Supply to LV & N
24VAC 50Hz Supply to LV & N
220VAC 50Hz Supply to A & N
240VAC 50Hz Supply to A & N
Inductive Motor Load
Maximum 68mA 1.63Watts
Maximum 108mA 2.34Watts
Maximum 87mA 2.00Watts
Maximum 94mA 2.54Watts
With Both Relays Closed 68mA Max at 12VDC 0.81W
With One Relay Closed 52mA Max at 12VDC 0.62W
Quiescent State (relays open) 25mA Max at 12VDC 0.30W
The F29 houses 2 relays. Relay 1 has S.P.D.T contacts. Relay 2 has S.P.S.T
normally open contacts. Relay 1 is normally regarded as the pump control
relay and relay 2 is normally regarded as the alarm relay.
With the HD terminal linked to the NO terminal of Relay 1, the F29 can
directly control a single phase motor up to 2.4kW via its NO contacts.
Without the HD terminal link in place, relays 1 & 2 are limited to directly
controlling a motor to 0.75kW.
Both relays can control motors of any
required size via interposing contactors.
16
IMPORTANT:
When directly controlling a pump motor through relay 1, always
link the HD terminal to relay 1 Normally Open terminal and make sure the
maximum switched motor current never exceeds 10 Amps. On a pump motor
P1 must not exceed 2.4kW.