F29 should be installed in a straight section of pipe preferably with 5
diameters of straight pipe either side of the paddle. The F29 can be
installed in a suitable pipe socket, tapping saddle or pipe tee.
The F29 can be installed in either the suction or discharge pipework of the
pump.
It is more common to install it in the discharge pipe, either before or
a
f
te
r
the system’s air cell. If the system includes an air cell a decision must
be made as to which side of the air cell to locate the flow switch. The way
the
overall sys
t
em functions will depend on this decision.