MY-A Series (10kVA-20kVA) UPS
User Manual
4 Touch Screen Operation
63
Item
Settable value
Battery static time (day)
1~30
Battery static delay time (h)
1~48
Battery backup function
On, Off
Single battery low-voltage protection (V/Cell)
1.667~1.867
Single battery test ending voltage (V/Cell)
1.667~1.867
Equalizing charge voltage of single battery (V/Cell) 2.083~2.417
Floating charge voltage of single battery (V/Cell)
2.083~2.333
Temperature compensation
On, Off
Temperature compensation coefficient (mV/℃)
0~5.0
Battery charge current (A)
10kVA: 1.0~10.0, default is 1A;
15kVA/20kVA: 1.0~20.0, default is
2A
Force equalizing charge
On
Click number input box, it will display the input range of setting value at the top of the input
keyboard. When the setting exceeds the range, the setting will be invalid. After setting, click "
" button to save the setting. Successful setting/unsuccessful setting mark is the same as that
of system management.
4.5.3 Battery Test Page
Battery test includes standard test and depth test and the battery test also can be canceled. The page
shows the test status, battery current, consumed capacity and test time. The battery test page is as
shown in Figure4-33.