A Technical Specifications
MY-A Series (10kVA-20kVA) UPS
User Manual
96
A
Technical Specifications
Model
Index
10kVA
15kVA
20kVA
Input
Input mode
3W+N+PE
Voltage range (Vac)
When the input voltage in the range of 90~155, the UPS can
bear load of 100% rated power;
When the input voltage in the range of 70-90, the output of the
UPS needs to decrease rated power linearly to use
Frequency range (Hz)
39.5~70.5
Bypass synchronism track
range (Hz)
50/60±10% (50/60 self-adaption)
Bypass input voltage range
(Vac)
10%/15%/20% (default is 20%)
Input power factor
≥0.99
Input THDI
Resistive full load: ≤3%; non-linear full load: ≤5%
Battery voltage (Vdc)
±96~±120 (can be selected from ±48 cells~±60 cells, default is
±60 cells, 2V/cell)
Charge current (A)
1~10 settable
(default is 1)
1~20 settable (default is 2)
O
ut
put
Output mode
3W +N+PE
Capacity (kVA/kW)
10/10
15/15
20/20