Rev. 1.00
22586_EDEBD
A0253-0318-1_EN
63
KBR multicomp F144-3 6DO/6RO
xx xx xx xx
Voltage 13
rd
harmonic
xx %
xx xx xx xx
Maximum missing compensation power
xx var
xx xx xx xx
Relay states (12 bit: bit 0 = stage 1 - bit 11 =
stage 12 // bit 13 = error message)
xx
yy yy
CRC code
13.6
Device information
The device information is read via the command 0x2B (Read Device Identifica-
tion)
Information about the manufacturer, device code and device version is read
in the process. The device supplies the "Basic Device Identification". "Regular"
and "Extended Device Identification" are optional according to the Modbus
definition.
Example Modbus RTU
Request:
01 2B 0E 01 00 70 77
in which
01
Device address
2B
Command
0E
MEI type according to the Modbus definition always 0x0E
01
Device ID code for "Basic Device Identification" (see Modbus
definition)
00
Object ID -> in our example manufacturer name, product name
and version
70 77
CRC code
Response:
01 2B 0E 01 01 00 00 03 00 08 4B 42 52 20 47 6D 62 48 01 12 4D 75 6C 74 69 6D
65 73 73 20 43 6F 6D 66
6F 72 74 02 09 20 32 2E 30 30 72 31 30 30 yy yy