13.3
Interface parameters
Baud rate (baud)
Parity
Data bits
Stop bits
4800,9600,19200,
38400
even, odd, none
8
2 for parity none
otherwise 1
The maximum data length of a Modbus transmission is 256 bytes. This results in
a user data length of 253 bytes.
The number of data bits and stop bits is defined in the Modbus definition. Baud
rates of less than 4800 baud are possible by definition, but not implemented at
present. The interface parameters can only be configured on the device (not via
bus).
13.4
Device settings
The settings are read with the 0x04 command (read input registers) in accordance with
table 1. Writing is not possible at present.
Address Words Description
Value
Format
0xD002
2
Primary transformer measuring voltage 0 - 999999 V
float
0xD004
2
Secondary transformer measuring
voltage
0 - 999 V
float
0xD006
2
Primary transformer measuring current 0 - 999999 A
float
0xD008
2
Secondary transformer measuring
current
1 A / 5 A
float
0xD00 A 2
Target CosPhi 1
-1.0 - +1.0
float
0xD00C 2
float
0xD00E
2
Target CosPhi for energy recovery
(fixed setting)
-1.0 - +1.0
float
0xD010
2
Target CosPhi for message
"PFC too small”
-1.0 - +1.0
float
0xD012
2
Connected phase
voltage measurement
0=L1N // 1=L2N
// 2=L3N // 4=L12
// 5=L23 // 6=L31
unsigned
long
0xD014
2
Connected phase current measurement 0=L1 // 1=L2 //
2=L3 // 3=-L1 //
4=-L2 // 5=-L3
unsigned
long
0xD016
2
0xD018
2
0xD01a
2
0xD01c
2
0xD01e
2
General