 2

An insufficient power supply capacity or inappropriate installation may 
cause fire. 

Use the specified cables for wiring connect the terminals 

securely fix. To prevent external forces applied to the terminals 

from affecting the terminals. 

Be sure to provide grounding. 

Do not connect ground wires to gas pipes, water pipes, lightning rods 
or ground wires for telephone cables. 

Conform to the regulations of the local electric company when 

wiring the power supply. 

Inappropriate grounding may cause electric shock. 

Do not install the air conditioner in a location subject to a risk of 

exposure to a combustible gas. 

If a combustible gas leaks, and stays around the unit, a fire may occur.

Required tools for installation work 

1) Philips screw driver 
2) Hole core drill(65mm) 
3) Spanner 
4) Pipe cutter 
5) Knife 
6) Reamer 
7) Gas leak detector 
8) Tape measure 
9) Thermometer 
10) Mega-tester 
11) Electro circuit tester 
12) Hexagonal wrench 
13) Flare tool 
14) Pipe bender 
15) Level vial 
16) Metal saw 
17) Gauge manifold (Charge hose:R410A special requirement) 
18) Vacuum pump (Charge hose:R410A special requirement) 
19) Torque wrench 

1/4(17mm)16N•m (1.6kgf•m) 
3/8(22mm)42N•m (4.2kgf•m) 
1/2(26mm)55N•m (5.5kgf•m) 
5/8(15.9mm)120N•m (12.0kgf•m) 

20) Copper pipe gauge adjusting projection margin 
21) Vacuum pump adapter 

2.  ATTACHED FITTINGS 

Please check whether the following fittings are of full scope. If there 
are some spare fittings , please restore them carefully. 

INSTALLATION 
FITTINGS

NAME

SHAPE

QUANTITY

1. Outdoor unit 
installation manual

1

2. Outdoor unit owner’s 
manual

1

3. TECHNICAL DATE 
MANUAL

1

4. ERP INFORMATION 
MANUAL

1

5. Water outlet pipe 

connector

1

6. Seal ring(8kW)

1

7. Rubber wire ring 
(10/12kW)

2

8. Network matching 
wires

2

9. Connecting pipe 
(16kW)

1

10. L-shaped pipe(14kW)

1

 NOTE 

 

z

Check if any accessory in the above figure is missing. All the 

accessories must be kept properly. 

 

z

All the fittings should be Kaysun fittings. 

 

z

Wired/Remote controller — purchase separately. 

 

z

Outlet sealant — purchase separately. 

 

z

All the figures in the manual explain only the general appearance 
and dimensions of the unit. The air conditioner you purchased may 
not be completely consistent with the appearance and functions 
listed in the figures. Please refer to the actual product. 

Refrigerant Piping 

Piping kit used for the conventional refrigerant cannot be used. 
Use copper pipe with 0.8 mm or more thickness for φ9.5. 
Use copper pipe with 1.0 mm or more thickness for φ15.9. 
Use copper pipe with 1.0 mm or more thickness for φ19.0. 
Flare nut and flare works are also different form those of the 
conventional refrigerant.take out the flare nut attached to the main unit 
of the air conditioner, and use it. 

Before installation 

Be careful to the following items before installation.

Air purge 

For air purge, use a vacuum pump. 
Do not use refrigerant charged in the outdoor unit for air purge. (The 
refrigerant for air purge is not contained in the outdoor unit.)

Electrical cabling 

Be sure to fix the power cables and indoor/outdoor connecting cables 
with clamps so that they do not contact with the cabinet, etc.

Installation Place 

A place which provides a specified space around the outdoor unit. 
A place were the operation noise and discharged air are not given to 
your neighbors. 
A place that is not exposed to a strong wind. 
A place that does not block a passage. 
When the outdoor unit is installed in an elevated position, make sure 
it’s four feet securely installed. 
There must be sufficient space for carrying in the unit. 
A place where the drain water does not make any problem. 

Summary of Contents for KMF-120 DVN4

Page 1: ...chasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference Mini Amazon III KMF 80 DVN4 KMF 100 DVN4 KMF 120 DVN4 KMF 140 DVN4 KMF 160 DVN4 INSTALLATION MANUAL ...

Page 2: ...nnection device which has at least 3mm separation distance in all pole and a residual current device RCD with the rating of above 10mA shall be incorporated in the fixed wiring according to the national rule The power cord type designation is H05RN R H07RN F or above Ask an authorized dealer or qualified installation professional to install maintain the air conditioner Inappropriate installation m...

Page 3: ...kW 2 8 Network matching wires 2 9 Connecting pipe 16kW 1 10 L shaped pipe 14kW 1 NOTE z Check if any accessory in the above figure is missing All the accessories must be kept properly z All the fittings should be Kaysun fittings z Wired Remote controller purchase separately z Outlet sealant purchase separately z All the figures in the manual explain only the general appearance and dimensions of th...

Page 4: ...ne may be caused There is combustible gas leakage There is much oil including engine oil ingredient There is salty air surrounding near the coast There is caustic gas the sulfide for example existing in the air near a hotspring A place the heat air expelled out from the outdoor unit can reach your neighbor s window A place that the noise interferes your neighbors every day life A place that is too...

Page 5: ...nlet surface Air inlet surface Maintenance cable and pipeline surface 2000 500 3000 3000 300 600 2000 300 3 3 Moving and installation Since the gravity center of the unit is not at its physical center so please be careful when lifting it with a sling Never hold the inlet of the outdoor unit to prevent it from deforming Do not touch the fan with hands or other objects Do not lean it more than 45 an...

Page 6: ...utlet plate The method of the out pipe in the same way of the back out pipe Undersurface outlet pipe the knock out should from inside to outside and then piping and wiring through this Pay attention to the piping the fat connecting pipe should out from the largest hole otherwise the pipes will be rubbed Please do the moth proofing for the knocked out hole to avoid the pest processing into and dest...

Page 7: ...9 5 KCMI 112 160 A 230 Φ19 1 Φ9 5 KCMI 112 4 5 Confirmation for the diameters of outdoor unit connecting pipes R410A outdoor unit connecting pipes diameters Table 4 4 Total capa ctiy of The outdoor units Main pipe size when the total equivalent piping length of liquid air side is 90m Main pipe size when the total equivalent piping length of liquid air side is 90m air side mm liquid side mm The fir...

Page 8: ...ion please refers to Table4 6 Note The max length of the branch pipe should not longer than 15m z The main pipes of indoor unit and the indoor unit branch pipe components The downstream inner units of the main pipe L2 are N1 N2 and its total capacity is 28 2 56 the size of pipe L2 isΦ15 9 Φ9 5 and the branch pipe B should be KCMI 112 The downstream inner units of the main pipe L4 are N3 N4 and its...

Page 9: ...r Unit Outdoor Unit Drop Height H Outdoor Unit up 10m 8kW 25m 10 12kW 30m 14 16kW Outdoor Unit Down 10m 8kW 20m 10 12kW 20m 14 16kW Indoor Unit to Indoor Unit Drop Heihgt H 8m Note When the total equivalent piping length of liquid gas side is 90m it must increase the size of air side main pipe Besides according to the distance of refrigerant pipe and the over matched state of inner unit when the c...

Page 10: ...of the vacuum gauge rises If the reading rises there is residual water or gas leakage in the system The leakage must be checked and solved and the test should be performed again z Water may enter into pipes in the following conditions the installation is carried out in rainy seasons and the installation period is long the pipes are condensed inside rainwater enters the pipes z After the above vacu...

Page 11: ...198 198 198 198 Max V 264 264 264 264 264 MCA 21 25 28 75 35 40 40 TOCA 18 1A 24A 29A 33A 33A MFA 25 32 40 40 40 Compressor MSC Soft star Soft star Soft star Soft star Soft star RLA 9 45 9 45 15 5 15 5 15 5 OFM kW 0 08 0 17 0 17 0 17 0 17 FLA 1 0 1 52 1 52 1 52 1 52 indoor unit power of one system into the same branch circuit z Please put the connective wire system between indoor unit and outdoor ...

Page 12: ... for 8kW and reserved digital multimeter interface for 10kW 12kW 14kW and 16kW The arrangement of OAE XYE and PQE depends on the unit Note The wired controller and centralized controller in the dashed box are optional accessories If necessary please contact the local distributor for purchase Fig 5 4 IDU IDU IDU IDU ODU P Q E P Q E P Q E Build out resistor Remote controller Wired controller P Q E P...

Page 13: ...ble 5 3 Rated current of appliance A Nominal cross sectional area mm Flexible cords Cable for fixed wiring 3 0 5 and 0 75 1 to 2 5 3 and 6 0 75 and 1 1 to 2 5 6 and 10 1 and 1 5 1 to 2 5 10 and 16 1 5 and 2 5 1 5 to 4 16 and 25 2 5 and 4 2 5 to 6 25 and 32 4 and 6 4 to 10 32 and 50 6 and 10 6 to 16 50 and 63 10 and 16 10 to 25 5 2 2 The method of fixing the power cord and signal line 1 The method ...

Page 14: ... connected to the power for 12hr z Test running can not start until all the valves are affirmed open z Never make the forced running Or the protector sits back danger will occur 7 PRECAUTIONS ON REFRIGERANT LEAKAGE This air conditioner A C adopts inncouous and nonflammable refrigerant The locating room of the A C should big engough that any refrigerant leakage is unable to reach critical thickness...

Page 15: ...or equipment that contains fluorinated greenhouse gases in quantities of 50 tonnes of CO2 equivalent or more but of less than 500 tonnes of CO2 equipment at least every six months or where a leakage detection system is installed at least every 12 months 3 For equipment that contains fluorinated greenhouse gases in quantities of 500 tonnes of CO2 equivalent or more at least every three months or wh...

Page 16: ......