 12

 

CAUTION

 

z

When the power cable is parallel to the signal wire, make sure 

that they are enclosed in respective conduits and are kept a 

reasonable wire spacing. (Distance between power cables: less 

than 10A-300mm;less than 50A-500mm)

 

z

The three-core shielded cable is used as the signal cables of the 

IDUs and ODU, and the shield layer must be grounded as required.

 

z

The display box and build-out resistor are IDU accessories. The 

remote controller, centralized controller and wired controller are 

optional accessories. If necessary, contact the local distributor for 

purchase. (Note: The BP3 series IDUs provide standard remote 

controllers.)

5.2  Indoor Unit Wiring

 

„

Power Supply

Table 5-2

Capicity(kW)

1.8~16

Indoor Unit 

Power

Phase

1-Phase

Voltage and 

Frequency

220-240V~ 50Hz

Power Wiring Size

Refer to Table 5-3 for wire size

Circuit Breaker (A)

16

Indoor Unit /Outdoor Unit Signal 
Wire (mm²) (Weak electric 
signal)

3-core shielded wire 3X0.75

5.2.1 

Safety device requirements

1.  Select the wire diameters( minimum value) individually for each 

unit based on the table 5-1 and table 5-2, where the rated current 
in table 5-1 means MCA in table 5-3. In case the MCA exceeds 
40A, the wire diameters should be selected according to the 
national wiring regulation.

2.  Maximum allowable voltage range variation between phases is 2%.
3.  Select circuit breaker that having a contact separation in all poles 

not less than 3 mm providing full disconnection, where MFA is used 
to select the current circuit breakers and residual current operation 
breakers:

Table 5-3

Rated current of 

appliance (A)

Nominal cross-sectional area (mm²)

Flexible cords

Cable for fixed wiring

≤3

0.5 and 0.75

1 to 2.5

>3 and ≤6

0.75 and 1

1 to 2.5

>6 and ≤10

1 and 1.5

1 to 2.5

>10 and ≤16

1.5 and 2.5

1.5 to 4

>16 and ≤25

2.5 and 4

2.5 to 6

>25 and ≤32

4 and 6

4 to 10

>32 and ≤50

6 and 10

6 to 16

>50 and ≤63

10 and 16

10 to 25

5.2.2 

The method of fixing the power cord and signal line: 

1. The method of fixing the power cord :

 

        8kw                           10/12kw                              14/16kw                                 

      

 

     8kw                                  10/12kw                             14/16kw

PQE

OAE

XYE

2. The method of fixing the signal wire :

 

        8kw                           10/12kw                              14/16kw                                 

      

 

     8kw                                  10/12kw                             14/16kw

PQE

OAE

XYE

The fixed mode of signal wire 8kw and 14/16kw is shown in the figure. 
The signal wire goes through the wire clamp, and the cable is tightly 
tied to the clamp with a belt to prevent the signal wire from moving up 
and down.

Single phase indoor unit

Wire controller

The reserved wire control

function is indicated in broken 

line table, users can purchase 

the wire controller when 

necessary.

To wire controller

 

Display 

board

WHITE

BLUE

BLACK

P Q

X Y E

YELLOW 

GRA

Y

To Outdoor 

COMM.BUS 

To Central Control

Monitor (CCM)

COMM. BUS 

Power  Supply

Y/G

N

L

Please use 3-core shielded  wire, and 

connect the shielded layer to Grounding 

XT1

XT3

Fig. 5-5

BLACK

E

1.  Signal wire is 3-core, polarized wire. Use 3-core shield wire to 

prevent interference. The grounding method now is grounding the 
closed end of the shield wire and opening (insulating) at the end. 
Shield is to be grounded.

2.  The control between outdoor unit and indoor unit is BUS type. 

Addresses is set on field during the installation.

 

CAUTION

Indoor/Outdoor unit signal wire is low voltage circuit. Do not let it 
touch the high voltage power wire and put it to gather with power 
cord in the same wire distribution pipe.

Summary of Contents for KMF-120 DVN4

Page 1: ...chasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference Mini Amazon III KMF 80 DVN4 KMF 100 DVN4 KMF 120 DVN4 KMF 140 DVN4 KMF 160 DVN4 INSTALLATION MANUAL ...

Page 2: ...nnection device which has at least 3mm separation distance in all pole and a residual current device RCD with the rating of above 10mA shall be incorporated in the fixed wiring according to the national rule The power cord type designation is H05RN R H07RN F or above Ask an authorized dealer or qualified installation professional to install maintain the air conditioner Inappropriate installation m...

Page 3: ...kW 2 8 Network matching wires 2 9 Connecting pipe 16kW 1 10 L shaped pipe 14kW 1 NOTE z Check if any accessory in the above figure is missing All the accessories must be kept properly z All the fittings should be Kaysun fittings z Wired Remote controller purchase separately z Outlet sealant purchase separately z All the figures in the manual explain only the general appearance and dimensions of th...

Page 4: ...ne may be caused There is combustible gas leakage There is much oil including engine oil ingredient There is salty air surrounding near the coast There is caustic gas the sulfide for example existing in the air near a hotspring A place the heat air expelled out from the outdoor unit can reach your neighbor s window A place that the noise interferes your neighbors every day life A place that is too...

Page 5: ...nlet surface Air inlet surface Maintenance cable and pipeline surface 2000 500 3000 3000 300 600 2000 300 3 3 Moving and installation Since the gravity center of the unit is not at its physical center so please be careful when lifting it with a sling Never hold the inlet of the outdoor unit to prevent it from deforming Do not touch the fan with hands or other objects Do not lean it more than 45 an...

Page 6: ...utlet plate The method of the out pipe in the same way of the back out pipe Undersurface outlet pipe the knock out should from inside to outside and then piping and wiring through this Pay attention to the piping the fat connecting pipe should out from the largest hole otherwise the pipes will be rubbed Please do the moth proofing for the knocked out hole to avoid the pest processing into and dest...

Page 7: ...9 5 KCMI 112 160 A 230 Φ19 1 Φ9 5 KCMI 112 4 5 Confirmation for the diameters of outdoor unit connecting pipes R410A outdoor unit connecting pipes diameters Table 4 4 Total capa ctiy of The outdoor units Main pipe size when the total equivalent piping length of liquid air side is 90m Main pipe size when the total equivalent piping length of liquid air side is 90m air side mm liquid side mm The fir...

Page 8: ...ion please refers to Table4 6 Note The max length of the branch pipe should not longer than 15m z The main pipes of indoor unit and the indoor unit branch pipe components The downstream inner units of the main pipe L2 are N1 N2 and its total capacity is 28 2 56 the size of pipe L2 isΦ15 9 Φ9 5 and the branch pipe B should be KCMI 112 The downstream inner units of the main pipe L4 are N3 N4 and its...

Page 9: ...r Unit Outdoor Unit Drop Height H Outdoor Unit up 10m 8kW 25m 10 12kW 30m 14 16kW Outdoor Unit Down 10m 8kW 20m 10 12kW 20m 14 16kW Indoor Unit to Indoor Unit Drop Heihgt H 8m Note When the total equivalent piping length of liquid gas side is 90m it must increase the size of air side main pipe Besides according to the distance of refrigerant pipe and the over matched state of inner unit when the c...

Page 10: ...of the vacuum gauge rises If the reading rises there is residual water or gas leakage in the system The leakage must be checked and solved and the test should be performed again z Water may enter into pipes in the following conditions the installation is carried out in rainy seasons and the installation period is long the pipes are condensed inside rainwater enters the pipes z After the above vacu...

Page 11: ...198 198 198 198 Max V 264 264 264 264 264 MCA 21 25 28 75 35 40 40 TOCA 18 1A 24A 29A 33A 33A MFA 25 32 40 40 40 Compressor MSC Soft star Soft star Soft star Soft star Soft star RLA 9 45 9 45 15 5 15 5 15 5 OFM kW 0 08 0 17 0 17 0 17 0 17 FLA 1 0 1 52 1 52 1 52 1 52 indoor unit power of one system into the same branch circuit z Please put the connective wire system between indoor unit and outdoor ...

Page 12: ... for 8kW and reserved digital multimeter interface for 10kW 12kW 14kW and 16kW The arrangement of OAE XYE and PQE depends on the unit Note The wired controller and centralized controller in the dashed box are optional accessories If necessary please contact the local distributor for purchase Fig 5 4 IDU IDU IDU IDU ODU P Q E P Q E P Q E Build out resistor Remote controller Wired controller P Q E P...

Page 13: ...ble 5 3 Rated current of appliance A Nominal cross sectional area mm Flexible cords Cable for fixed wiring 3 0 5 and 0 75 1 to 2 5 3 and 6 0 75 and 1 1 to 2 5 6 and 10 1 and 1 5 1 to 2 5 10 and 16 1 5 and 2 5 1 5 to 4 16 and 25 2 5 and 4 2 5 to 6 25 and 32 4 and 6 4 to 10 32 and 50 6 and 10 6 to 16 50 and 63 10 and 16 10 to 25 5 2 2 The method of fixing the power cord and signal line 1 The method ...

Page 14: ... connected to the power for 12hr z Test running can not start until all the valves are affirmed open z Never make the forced running Or the protector sits back danger will occur 7 PRECAUTIONS ON REFRIGERANT LEAKAGE This air conditioner A C adopts inncouous and nonflammable refrigerant The locating room of the A C should big engough that any refrigerant leakage is unable to reach critical thickness...

Page 15: ...or equipment that contains fluorinated greenhouse gases in quantities of 50 tonnes of CO2 equivalent or more but of less than 500 tonnes of CO2 equipment at least every six months or where a leakage detection system is installed at least every 12 months 3 For equipment that contains fluorinated greenhouse gases in quantities of 500 tonnes of CO2 equivalent or more at least every three months or wh...

Page 16: ......

Reviews: