4.4  Connecting method 

 

„

Select refrigerant pipe 

Table 4-2

Pipe definition

Pipe connect position

Code

Main pipe

The pipe between outdoor unit to the 
first branch of indoor unit.

L1

The main pipes of 
indoor unit

The pipe after the first branch do not 
drect connect with the indoor unit.

L2~L5

The branch pipes 
of indoor unit

The pipe after the branch connect with 
the indoor unit.

a,b,c, 

d,e,f

Indoor unit branch 
pipes components

The pipes connect with the main pipe 
the branch pipe and the the main pipe 
of indoor unit.

A,B,C, 

D,E

a

b

c

e

f

d

L

1

L

2

L

3

L

4

L

5

A

B

C

D

E

N

1

(28)

N

3

(28)

N

5

(28)

N

6

(22)

N

2

(28)

N

4

(28)

A

B

D

E

C

a

b

c

e

f

d

L

1

L

2

L

5

L

3

L

4

The First Line Branch Pipe

Outdoor Unit

The First Line Branch Pipe

Intdoor Units

Fig. 4-4

Fig. 4-5

 NOTE

 

z

Use the special-purpose branch branches provided by Kaysun 

only. Failing to do so may lead to severe system malfunction. 

 

z

If the distance from the first branch pipe to the last IDU exceeds 15 

m, use connection method 2. 

 

z

The connection distance between the IDU and branch pipe should 

not exceed 15 m.

4.4  Confirmation for the diameters of indoor 

unit connecting pipes

1) R410A Indoor unit connecting pipes diameters 4-3.
2) Example 1: In the Fig.4-5,The downstream inner units of the L2,and 
its total capacity is 28×2=56, refers to the Table 4.4,the air/liquid side 
of L2 is: Φ15.9/Φ9.5.

R410A Indoor unit connecting pipes diameters 

 

Table 4-3

Total capactiy of the 
downstream inner units

Main pipe size (mm)

Branch Pipe

Air pipe

Iiquid pipe

A≤160

Φ15.9

Φ9.5

KCMI 112

160≤A<230

Φ19.1

Φ9.5

KCMI 112

4.5  Confirmation for the diameters of outdoor 

unit connecting pipes

R410A outdoor unit connecting pipes diameters   

Table 4-4

Total capa- 

ctiy of The 

outdoor 

units

Main pipe size when the total 

equivalent piping length of air 

side is <90m

Main pipe size when the total 

equivalent piping length of air 

side is ≥90m

air side 

(mm)

liquid side 

(mm)

The first Line 

Branch Pipe

air side 

(mm)

liquid side 

(mm)

The first Line 

Branch Pipe

A<155

Φ15.9

Φ9.5

KCMI 112

Φ19.1

Φ9.5

KCMI 112

155≤A<230

Φ19.1

Φ9.5

KCMI 112

Φ22.2

Φ9.5

KCMI 212

 NOTE

 

z

The straight distance between copper pipe turning and the co 

ntiguous branch pipe is at least 0.5 m. 

 

z

The straight distance between the contiguous branch pipes is at 

least 0.5 m. 

 

z

The straight distance which the branch pipes connected to the IDU 

is at least 0.5 m.

 

z

Select branch joint  

Select the branch joint according to the total designed capacity of 

indoor units which it connects to. If this capacity is more than that 

of the outdoor unit, then select the connection according to the 

outdoor unit. 

 

z

The selection of branch header depends on the quantity of 

branches it connects to.

 

„

Connection method 

Table 4-5

Gas side

Liquid side

8kW

Flaring

Flaring

10kW

Welding or Flaring

Flaring

12kW

Welding or Flaring

Flaring

14kW

Welding or Flaring

Flaring

16kW

Welding or Flaring

Flaring

Indoor unit

Flaring

Flaring

Branch pipe

Welding or Flaring

Welding or Flaring

 

„

Piping sizes at the branch pipe 

Table 4-6

Refrigerant 

Indoor Unit 

Capacity 

A(x100W)

Gas Side (Φ)

Liquid Side (Φ)

R410A 

A≤45

12.7(Flaring nut)  6.4(Flaring nut)

A≥56

15.9(Flaring nut)  9.5(Flaring nut)

 

z

The first connect methond 

 

z

The second connect methond 

Summary of Contents for KMF-120 DVN4

Page 1: ...chasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference Mini Amazon III KMF 80 DVN4 KMF 100 DVN4 KMF 120 DVN4 KMF 140 DVN4 KMF 160 DVN4 INSTALLATION MANUAL ...

Page 2: ...nnection device which has at least 3mm separation distance in all pole and a residual current device RCD with the rating of above 10mA shall be incorporated in the fixed wiring according to the national rule The power cord type designation is H05RN R H07RN F or above Ask an authorized dealer or qualified installation professional to install maintain the air conditioner Inappropriate installation m...

Page 3: ...kW 2 8 Network matching wires 2 9 Connecting pipe 16kW 1 10 L shaped pipe 14kW 1 NOTE z Check if any accessory in the above figure is missing All the accessories must be kept properly z All the fittings should be Kaysun fittings z Wired Remote controller purchase separately z Outlet sealant purchase separately z All the figures in the manual explain only the general appearance and dimensions of th...

Page 4: ...ne may be caused There is combustible gas leakage There is much oil including engine oil ingredient There is salty air surrounding near the coast There is caustic gas the sulfide for example existing in the air near a hotspring A place the heat air expelled out from the outdoor unit can reach your neighbor s window A place that the noise interferes your neighbors every day life A place that is too...

Page 5: ...nlet surface Air inlet surface Maintenance cable and pipeline surface 2000 500 3000 3000 300 600 2000 300 3 3 Moving and installation Since the gravity center of the unit is not at its physical center so please be careful when lifting it with a sling Never hold the inlet of the outdoor unit to prevent it from deforming Do not touch the fan with hands or other objects Do not lean it more than 45 an...

Page 6: ...utlet plate The method of the out pipe in the same way of the back out pipe Undersurface outlet pipe the knock out should from inside to outside and then piping and wiring through this Pay attention to the piping the fat connecting pipe should out from the largest hole otherwise the pipes will be rubbed Please do the moth proofing for the knocked out hole to avoid the pest processing into and dest...

Page 7: ...9 5 KCMI 112 160 A 230 Φ19 1 Φ9 5 KCMI 112 4 5 Confirmation for the diameters of outdoor unit connecting pipes R410A outdoor unit connecting pipes diameters Table 4 4 Total capa ctiy of The outdoor units Main pipe size when the total equivalent piping length of liquid air side is 90m Main pipe size when the total equivalent piping length of liquid air side is 90m air side mm liquid side mm The fir...

Page 8: ...ion please refers to Table4 6 Note The max length of the branch pipe should not longer than 15m z The main pipes of indoor unit and the indoor unit branch pipe components The downstream inner units of the main pipe L2 are N1 N2 and its total capacity is 28 2 56 the size of pipe L2 isΦ15 9 Φ9 5 and the branch pipe B should be KCMI 112 The downstream inner units of the main pipe L4 are N3 N4 and its...

Page 9: ...r Unit Outdoor Unit Drop Height H Outdoor Unit up 10m 8kW 25m 10 12kW 30m 14 16kW Outdoor Unit Down 10m 8kW 20m 10 12kW 20m 14 16kW Indoor Unit to Indoor Unit Drop Heihgt H 8m Note When the total equivalent piping length of liquid gas side is 90m it must increase the size of air side main pipe Besides according to the distance of refrigerant pipe and the over matched state of inner unit when the c...

Page 10: ...of the vacuum gauge rises If the reading rises there is residual water or gas leakage in the system The leakage must be checked and solved and the test should be performed again z Water may enter into pipes in the following conditions the installation is carried out in rainy seasons and the installation period is long the pipes are condensed inside rainwater enters the pipes z After the above vacu...

Page 11: ...198 198 198 198 Max V 264 264 264 264 264 MCA 21 25 28 75 35 40 40 TOCA 18 1A 24A 29A 33A 33A MFA 25 32 40 40 40 Compressor MSC Soft star Soft star Soft star Soft star Soft star RLA 9 45 9 45 15 5 15 5 15 5 OFM kW 0 08 0 17 0 17 0 17 0 17 FLA 1 0 1 52 1 52 1 52 1 52 indoor unit power of one system into the same branch circuit z Please put the connective wire system between indoor unit and outdoor ...

Page 12: ... for 8kW and reserved digital multimeter interface for 10kW 12kW 14kW and 16kW The arrangement of OAE XYE and PQE depends on the unit Note The wired controller and centralized controller in the dashed box are optional accessories If necessary please contact the local distributor for purchase Fig 5 4 IDU IDU IDU IDU ODU P Q E P Q E P Q E Build out resistor Remote controller Wired controller P Q E P...

Page 13: ...ble 5 3 Rated current of appliance A Nominal cross sectional area mm Flexible cords Cable for fixed wiring 3 0 5 and 0 75 1 to 2 5 3 and 6 0 75 and 1 1 to 2 5 6 and 10 1 and 1 5 1 to 2 5 10 and 16 1 5 and 2 5 1 5 to 4 16 and 25 2 5 and 4 2 5 to 6 25 and 32 4 and 6 4 to 10 32 and 50 6 and 10 6 to 16 50 and 63 10 and 16 10 to 25 5 2 2 The method of fixing the power cord and signal line 1 The method ...

Page 14: ... connected to the power for 12hr z Test running can not start until all the valves are affirmed open z Never make the forced running Or the protector sits back danger will occur 7 PRECAUTIONS ON REFRIGERANT LEAKAGE This air conditioner A C adopts inncouous and nonflammable refrigerant The locating room of the A C should big engough that any refrigerant leakage is unable to reach critical thickness...

Page 15: ...or equipment that contains fluorinated greenhouse gases in quantities of 50 tonnes of CO2 equivalent or more but of less than 500 tonnes of CO2 equipment at least every six months or where a leakage detection system is installed at least every 12 months 3 For equipment that contains fluorinated greenhouse gases in quantities of 500 tonnes of CO2 equivalent or more at least every three months or wh...

Page 16: ......

Reviews: