CONTENTS  ...................................................................... PAGE 

PRECAUTIONS ........................................................................ 1 
ATTACHED FITTINGS .............................................................. 2 
OUTDOOR UNIT INSTALLATION ............................................. 3 
INSTALL THE CONNECTING PIPE .......................................... 5 
ELECTRICAL WIRING ............................................................ 10 
TEST RUNNING...................................................................... 13 
PRECAUTIONS ON REFRIGERANT LEAKAGE.................... 13 
TURN OVER TO CUSTOMER ................................................ 14 

1. PRECAUTIONS 

 

„

Ensure that all Local, National and International regulations 

are satisfied. 

 

„

Read this ”PRECAUTIONS ” carefully before Installation. 

 

„

The precautions described below include the important items 

regarding safety. Observe them without fail. 

 

„

After the installation work, perform a trial operation to check 

for any problem. 

 

„

Follow the Owner’s Manual to explain how to use and maintain 

the unit to the customer. 

 

„

Turn off the main power supply switch (or breaker) before 

maintenance the unit . 

 

„

Ask the customer that the Installation Manual and the Owner’s 

Manual should be kept together . 

 CAUTION 

New Refrigerant Air Conditioner Installation 

THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT(R410A)
WHICH DOES NOT DESTROY OZONE LAYER. 

The characteristics of R410A refrigerant are; Hydrophilic, oxid-

izing membrane or oil, and its pressure is approx.1.6 times high-

er than that of refrigerant R22.Accompanied with the new refrig-

erant, refrigerating oil has also been changed ,Therefore, during 

installation work, be sure that water, dust, former refrigerant, or 

refrigerating oil does not enter the refrigerating cycle. 

To prevent charging an incorrect refrigerant and refrigerating 

oil, the sizes of connecting sections of charging port of the 

main unit and installation tools are charged from those for the 

conventional refrigerant. 

Accordingly the exclusive tools are required for the new 

refrigerant (R410A): For connecting pipes, use new and clean 

piping designed for R410A,and please care so that water or dust 

does not enter. Moreover, do not use the existing piping because 

there are problems with pressure-resistance force and impurity 

in it. 

 

CAUTION 

Do not connect the Appliance from Main 

Power Supply. 

This unit must be connected to the main power supply by means 

of a switch with a contact separation of at least 3 mm. The 

installation fuse must be used for the power supply line of this 

conditioner. 

 WARNING 

If the supply cord is damaged, it must be replaced by the 

manufacturer or its service agent or a similarly qualified person 

in order to avoid a hazard. 

An all-pole disconnection switch having a contact separation of 

at least 3mm in all poles should be connected in fixed wiring. 

The appliance shall be installed in accordance with 

national 

wiring regulations. 

The temperature of refrigerant circuit will be high, please keep 

the interconnection cable away from the copper tube. 

An all-pole disconnection device which has at least 3mm 

separation distance in all pole and a residual current device(RCD)

with the rating of above 10mA shall be incorporated in the fixed 

wiring according to the national rule. 

The power cord type designation is H05RN-R/H07RN-F or above. 

Ask an authorized dealer or qualified installation professional to 

install/maintain the air conditioner. 

Inappropriate installation may result in water leakage,electric shock or 
fire. 

Turn off the main power supply switch or breaker before 

attempting any electrical work. 

Make sure all power switches are off.Failure to do so may cause 
electric shock. 

Connect the connecting cable correctly. 

If the connecting cable is connected in a wrong way, electric parts may 
be damaged. 

When moving the air conditioner for the installation into another 

place, be very careful not to enter any gaseous matter other than 

the specified refrigerant into the refrigeration cycle. 

If air or any other has is mixed in refrigerant, the gas pressure in the 
refrigeration cycle becomes abnormally high and it may resultingly 
causes pipe burst and injuries on persons. 

Do not modify this unit by removing any of the safety guards or 

by by-passing any of the safety interlock switches. 

Exposure of unit to water or other moisture before installation 

may cause a short-circuit of electrical parts. 

Do not store it in a wet basement or expose to rain or water. 

After unpacking the unit, examine it carefully if there are possible 

damage. 

Do not install in a place that might increase the vibration of the 

unit. 

To avoid personal injury (with sharp edges), be careful when 

handling parts. 

Perform installation work properly according to the Installation 

Manual. 

Inappropriate installation may result in water leakage, electric shock 
or fire. 

When the air conditioner is installed in a small room, provide 

appropriate measures to ensure that the concentration of 

refrigerant leakage occur in the room does not exceed the critical 

level. 

Install the air conditioner securely in a location where the 

base can sustain the weight adequately. Perform the specified 

installation work to guard against an earthquake. 

If the air conditioner is not installed appropriately, accidents may occur 
due to the falling unit. 

If refrigerant gas has leaked during the installation work, 

ventilate the room immediately. 

If the leaked refrigerant gas comes in contact with fire, noxious gas 
may generate. 

After the installation work, confirm that refrigerant gas doer not 

leak. 

If refeigerant gas leaks into the room and flows near a fire source, 
such as a cooking range, noxious gas might generate. 

Electrical work must be performed by a qualified electrician 

in accordance with the Installation Manual. Make sure the air 

conditioner uses an exclusive power supply. 

Equipment complying with IEC 61000-3-12 

Summary of Contents for KMF-120 DVN4

Page 1: ...chasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference Mini Amazon III KMF 80 DVN4 KMF 100 DVN4 KMF 120 DVN4 KMF 140 DVN4 KMF 160 DVN4 INSTALLATION MANUAL ...

Page 2: ...nnection device which has at least 3mm separation distance in all pole and a residual current device RCD with the rating of above 10mA shall be incorporated in the fixed wiring according to the national rule The power cord type designation is H05RN R H07RN F or above Ask an authorized dealer or qualified installation professional to install maintain the air conditioner Inappropriate installation m...

Page 3: ...kW 2 8 Network matching wires 2 9 Connecting pipe 16kW 1 10 L shaped pipe 14kW 1 NOTE z Check if any accessory in the above figure is missing All the accessories must be kept properly z All the fittings should be Kaysun fittings z Wired Remote controller purchase separately z Outlet sealant purchase separately z All the figures in the manual explain only the general appearance and dimensions of th...

Page 4: ...ne may be caused There is combustible gas leakage There is much oil including engine oil ingredient There is salty air surrounding near the coast There is caustic gas the sulfide for example existing in the air near a hotspring A place the heat air expelled out from the outdoor unit can reach your neighbor s window A place that the noise interferes your neighbors every day life A place that is too...

Page 5: ...nlet surface Air inlet surface Maintenance cable and pipeline surface 2000 500 3000 3000 300 600 2000 300 3 3 Moving and installation Since the gravity center of the unit is not at its physical center so please be careful when lifting it with a sling Never hold the inlet of the outdoor unit to prevent it from deforming Do not touch the fan with hands or other objects Do not lean it more than 45 an...

Page 6: ...utlet plate The method of the out pipe in the same way of the back out pipe Undersurface outlet pipe the knock out should from inside to outside and then piping and wiring through this Pay attention to the piping the fat connecting pipe should out from the largest hole otherwise the pipes will be rubbed Please do the moth proofing for the knocked out hole to avoid the pest processing into and dest...

Page 7: ...9 5 KCMI 112 160 A 230 Φ19 1 Φ9 5 KCMI 112 4 5 Confirmation for the diameters of outdoor unit connecting pipes R410A outdoor unit connecting pipes diameters Table 4 4 Total capa ctiy of The outdoor units Main pipe size when the total equivalent piping length of liquid air side is 90m Main pipe size when the total equivalent piping length of liquid air side is 90m air side mm liquid side mm The fir...

Page 8: ...ion please refers to Table4 6 Note The max length of the branch pipe should not longer than 15m z The main pipes of indoor unit and the indoor unit branch pipe components The downstream inner units of the main pipe L2 are N1 N2 and its total capacity is 28 2 56 the size of pipe L2 isΦ15 9 Φ9 5 and the branch pipe B should be KCMI 112 The downstream inner units of the main pipe L4 are N3 N4 and its...

Page 9: ...r Unit Outdoor Unit Drop Height H Outdoor Unit up 10m 8kW 25m 10 12kW 30m 14 16kW Outdoor Unit Down 10m 8kW 20m 10 12kW 20m 14 16kW Indoor Unit to Indoor Unit Drop Heihgt H 8m Note When the total equivalent piping length of liquid gas side is 90m it must increase the size of air side main pipe Besides according to the distance of refrigerant pipe and the over matched state of inner unit when the c...

Page 10: ...of the vacuum gauge rises If the reading rises there is residual water or gas leakage in the system The leakage must be checked and solved and the test should be performed again z Water may enter into pipes in the following conditions the installation is carried out in rainy seasons and the installation period is long the pipes are condensed inside rainwater enters the pipes z After the above vacu...

Page 11: ...198 198 198 198 Max V 264 264 264 264 264 MCA 21 25 28 75 35 40 40 TOCA 18 1A 24A 29A 33A 33A MFA 25 32 40 40 40 Compressor MSC Soft star Soft star Soft star Soft star Soft star RLA 9 45 9 45 15 5 15 5 15 5 OFM kW 0 08 0 17 0 17 0 17 0 17 FLA 1 0 1 52 1 52 1 52 1 52 indoor unit power of one system into the same branch circuit z Please put the connective wire system between indoor unit and outdoor ...

Page 12: ... for 8kW and reserved digital multimeter interface for 10kW 12kW 14kW and 16kW The arrangement of OAE XYE and PQE depends on the unit Note The wired controller and centralized controller in the dashed box are optional accessories If necessary please contact the local distributor for purchase Fig 5 4 IDU IDU IDU IDU ODU P Q E P Q E P Q E Build out resistor Remote controller Wired controller P Q E P...

Page 13: ...ble 5 3 Rated current of appliance A Nominal cross sectional area mm Flexible cords Cable for fixed wiring 3 0 5 and 0 75 1 to 2 5 3 and 6 0 75 and 1 1 to 2 5 6 and 10 1 and 1 5 1 to 2 5 10 and 16 1 5 and 2 5 1 5 to 4 16 and 25 2 5 and 4 2 5 to 6 25 and 32 4 and 6 4 to 10 32 and 50 6 and 10 6 to 16 50 and 63 10 and 16 10 to 25 5 2 2 The method of fixing the power cord and signal line 1 The method ...

Page 14: ... connected to the power for 12hr z Test running can not start until all the valves are affirmed open z Never make the forced running Or the protector sits back danger will occur 7 PRECAUTIONS ON REFRIGERANT LEAKAGE This air conditioner A C adopts inncouous and nonflammable refrigerant The locating room of the A C should big engough that any refrigerant leakage is unable to reach critical thickness...

Page 15: ...or equipment that contains fluorinated greenhouse gases in quantities of 50 tonnes of CO2 equivalent or more but of less than 500 tonnes of CO2 equipment at least every six months or where a leakage detection system is installed at least every 12 months 3 For equipment that contains fluorinated greenhouse gases in quantities of 500 tonnes of CO2 equivalent or more at least every three months or wh...

Page 16: ......