59
Part 4 - Diagnosis and T
roubleshooting
4.4 E2 Troubleshooting
4.4.1 Digital display output
4.4.2 Description
Communication error between outdoor unit and user interface.
All units stop running.
Error code is displayed on main PCB and user interface.
4.4.3 Possible causes
Communication wires between outdoor unit and user interface are not connected properly.
Communication wiring P Q E terminals misconnected.
Loosened wiring within electric control box.
Interference from high voltage wires or other sources of electromagnetic radiation.
Communication wire is too long.
Damaged main PCB, user interface or electric control box communication terminals block.