![Kaysun KEM-30 DRS4 Service Manual Download Page 53](http://html.mh-extra.com/html/kaysun/kem-30-drs4/kem-30-drs4_service-manual_659094053.webp)
52
P1
22
System low pressure protection
Displayed on main PCB and user
interface
P2
23
Tz/7 Coil final outlet temperature too high
Displayed on main PCB and user
interface
P3
24
T4 ambient temperature too high in cooling mode
Displayed on main PCB and user
interface
P4
25
System A current protection
Displayed on main PCB and user
interface
P5
26
System B current protection
Displayed on main PCB and user
interface
P6
27
Inverter module failure
Displayed on main PCB and user
interface
P7
28
High temperature protection of system condenser
Displayed on main PCB and user
interface
P9
30
Water inlet and outlet temperature difference protection
Displayed on main PCB and user
interface
Pb
32
Antifreeze protection in winter
Displayed on main PCB
PC
33
Evaporator pressure too low in cooling
Displayed on main PCB and user
interface
PE
35
Cooling evaporator low temperature antifreeze protection
Displayed on main PCB and user
interface
PH
37
T4 ambient temperature too high in heatling mode
Displayed on main PCB and user
interface
PL
38
Inverter module temperature Tfin too high temperature protection
Displayed on main PCB and user
interface
xPU
40
DC fan module protection
Displayed on main PCB and user
interface
H5
46
Voltage too high or too low
Displayed on main PCB and user
interface
xH9
50
Compressor inverter module is not matched
Displayed on main PCB and user
interface
xHE
55
Not insert electronic expansion valve
Displayed on main PCB and user
interface
xF0
61
IPM module communication failure
Displayed on main PCB
F2
63
Superheat insufficient
Displayed on main PCB and user
interface
xF4
65
L0 or L1 protection occurs 3 times in 60 minutes
Displayed on main PCB and user
interface
xF6
67
DC bus voltage error (PTC)
Displayed on main PCB and user
interface
F7
68
Not insert electronic expansion valve
Displayed on main PCB
xF9
70
Inverter module temperature sensor error
Displayed on main PCB and user
interface
Fb
72
Pressure sensor error
Displayed on main PCB and user
interface
Table 4-3.1: Error Code Table (30kW and 60kW units) (continued)
Table continued on next page …