6.10 Water Side Heat Exchanger Low Temperature Protection Control
This control protects the water side heat exchanger from ice formation.
Figure 3-6.12: Water side heat exchanger low temperature protection control in normal cooling mode
Normal operation
Min (Taf1 or Taf2) ≤ 3°C
Min (Taf1 and Taf2) >10°C
Low temperature protection, error code PE is
Notes:
1. Taf1: Water side heat exchanger anti-freezing temperature1
2. Taf2: Water side heat exchanger anti-freezing temperature2
When water side heat exchanger anti-freezing temperature1 (Taf1) or water side heat exchanger anti-freezing
temperature2 (Taf2) is at or below 3°C for more than 3 seconds, the system displays PE protection and the corresponding
unit stop running. When water side heat exchanger anti-freezing temperature1 (Taf1) and Water side heat exchanger anti-
freezing temperature2 (Taf2) rise to 10°C or higher, the compressor enters re-start control. Use the user interface to clear
the error.
Figure 3-6.13: Water side heat exchanger low temperature protection control in low outlet water mode
Normal operation
Min (Taf1 or Taf2) ≤ 0°C
Min (Taf1 and Taf2) > 5°C
Low temperature protection, error code PE is displayed
When water side heat exchanger anti-freezing temperature1 (Taf1) or water side heat exchanger anti-freezing
temperature2 (Taf2) is at or below 0°C for more than 3 seconds, the system displays PE protection and orders the
corresponding units to stop running. When water side heat exchanger anti-freezing temperature1 (Taf1) and Water side
heat exchanger anti-freezing temperature2 (Taf2) rise to 5°C or higher, the compressor enters re-start control. Use the user
interface to clear the error.
6.11 Water Side Heat Exchanger Low Pressure Protection Control
This control protects the water side heat exchanger from ice formation.
Figure 3-6.14: Water side heat exchanger low pressure protection control in normal cooling mode
Normal operation
Pe < 0.6Mpa for 30s
Pe ˃ 0.6Mpa
Low pressure protection, error code PC is
When system displays PC protection
and a manual system restart is
required before the system can
resume operation.
Notes:
1. Pe: Suction pressure
In normal cooling mode, when the suction pressure drops below 0.6Mpa for 30s, the system displays PC protection and