Installation & Owner's Manual
8
Water Affusion
Hot water outlet
Close
Water out
When water flows out from the water outlet,
the tank is full. Turn off the hot water outlet
valve and water affusion is finished.
Open
Open the cold water inlet valve and the hot
water outlet valve.
Cold water inlet
Hot water outlet
Open
Close
Open
Drainpipe shut-off valve
Open
Cold water inlet
Close the cold water inlet valve, open the hot
water outlet valve and open drainpipe.
Hot water outlet
Solar Pump
(300L)
Alarm
SW1 Factory Setting
for Disinfect
&Electric Heater
Model Selection
SW2 Factory Setting
for 190L/300L Model
Selection
High Pressure
Switch
Tp:Comp
Discharge
Temp.Sensor
Transformer
Output
Transformer
Input
Power Supply
Solar Input
(300L)
Fan COMP
4-way
Valve
EHEAT S.V. Crank
Heater
Panel Display
Power Supply
Output
Panel Display
Output
T5L:Lower
Tank Water
Temp.Sensor
T5U:Upper
Tank Water
Temp.Sensor
T4:Ambient
Temp.Sensor
T3:Evaporator
Inlet Temp.
Sensor
Th:Comp
Suction
Temp.Sensor
L
N
GND
Power Cable
Creepage Protector
Power Supply
EEV
3.3.4 Switch setting
PCB has 2 bits of switches.
Table.3-4
SW1
Model selection (User never allow to alter the factory settings)
ON
OFF
S W 1_1
Without Electric Heater
With Electric Heater
SW 1_2
Without Disinfect
With Disinfect
Table.3-5
SW2
Model selection (User never allow to alter the factory settings)
ON
OFF
S W 1_1
300L model
190L model
SW 1_2
Power furquency_60Hz
Power furquency_50Hz
3.3.5 Electric leakage protector
Fig.3-13
3.4 Installation checklist
3.4.1 Location
● The flooring beneath the water heater must be able to support
the weight of the unit when filled with water (more than 445kg).
● Located indoors (such as a basement or garage) and in a
vertical position. Sheltered from freezing temperatures.
● Provisions made to shelter the area from water damage.
Metal drain pan installed and piped to an adequate drain.
● Sufficient space to service the water heater.
● Sufficient air for the heat pump to function, the water heater
must be located in a space >15m³, and must have unrestricted
air flow.
WARNING
For optimal efficiency and service ability, the following clearances
should be maintained: 800mm on the air inlet side, 800mm on the
air outlet side, 600mm in the back, and 600mm in the front.
3.3.3 PCB I/O Ports description
Fig.3-12
Summary of Contents for COMPAK KHP 15/190 ACS1
Page 23: ......