34
kayden.com Online Store
CLASSIC
®
800 Product Manual
Setup & Operation
To View or Adjust the Set Points
1.
Press and release
SET
until the
Set Point 1
or
Set Point 2
LED is on solid and the
Run Mode
LED is off.
2.
One LED on the
Thermal Signal Bar Graph
will illuminate, corresponding to the present setting of the
selected set point.
3.
To adjust the selected
Set Point
, press and release the
Left
or
Right Arrow
keys.
4.
When satisfied with your configuration, press and release
SET
to continue to the next programmable
variable OR press and release
RUN
to return to
Run Mode
.
Figure 25 - Set Point 1 & 2 Configuration
Thermal Signal
100%
0
Relay 1
Relay 2
Fault
Set Point 1
Set Point 2
Run Mode
Bypass
RUN
SET
1
2
CLASSIC
™
Thermal Signal
100%
0
Relay 1
Relay 2
Fault
Set Point 1
Set Point 2
Run Mode
Bypass
RUN
SET
1
2
CLASSIC
™
Set Point 1 LED is ON
Set Point 2 LED is ON
Single LED
displays Set Point 1
Single LED
displays Set Point 2
Increase Set Point
Increase Set Point
Decrease Set Point
Decrease Set Point
3. View or Adjust Set Points 1 & 2
Notes: 1.
Viewing either
Set Point 1
or
2
from the Display Panel does not require entering the Manual Setup
Mode. While still in
RUN Mode
, press and hold
1
or
2
to view the programmed
Set Point
.
2.
In this context “Set Point” refers to the point(s) within the user defined range at which
Relay 1
and
Relay 2
energize/de-energize.
3.
Set Point 1
always corresponds to
Relay 1
and
Set Point 2
always corresponds to
Relay 2
.
4.
Relay energize/de-energize can be delayed by configuring relay delay timers. Refer to Modbus
Registers and Kayden RCM Software use in
Section 6
.